CHAPTER 10: INTRODUCING THE D400 CONFIGURATION
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
GE INFORMATION
125
Example System Configuration
Figure _ shows an example system configuration.
Figure 58: Sample system configuration
NOTE
†This field is configured in minutes, so the value entered in the configuration tool would be
-420 and -300 respectively. However, hours are shown in the diagram above for clarity.
Remote access
via web-based HMI
Local access to
command line via
RS232 port
Even though the
D400
device is located
in the local time zone of UTC -7, the
D400
system clock is set to UTC time.
Local device with
clock set to UTC -7
Remote client with clock
set to UTC -5
PC clock is set to
local time zone (
-8
)
No configuration
necessary
d400cfg System Clock:
UTC time
d400cfg Time Zone:
-7
DNP Client Map File
Time Offset
:
-7
†
DNP Server Application
Parameters
Time Offset
:
-5
†
If an event occurs at 13:00 UTC…
Event timestamp is
displayed as
05:00
Event timestamp is
displayed as
06:00
The
D400
system database records the
event timestamp as
13:00
Local device reports
the event at
06:00
Remote client receives the
event timestamp as
08:00
Summary of Contents for Multilin D400
Page 12: ...12 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL PRODUCT SUPPORT ...
Page 28: ...28 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 34: ...34 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 2 INSTALLING THE D400 ...
Page 88: ...88 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 5 POWERING UP THE D400 ...
Page 174: ...174 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX A STANDARDS PROTECTION ...
Page 184: ...184 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX C LIST OF ACRONYMS ...
Page 192: ...192 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL INDEX ...