178
GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
APPENDIX B INSTALLING AND CONNECTING DNP3 I/O MODULES
Connecting DNP3 I/O modules (Low Voltage)
For a Low Voltage (LV) DNP3 I/O module, connect the:
•
Interconnect cabling between each DNP3 I/O module, and
•
Power to the last DNP3 I/O module of the chain.
DNP3 I/O module (LV) interconnect cabling
The DNP3 I/O module interconnect cabling is shown in Figure 70.
Figure 70: Interconnect cabling between each DNP3 I/O module and power (LV)
After DNP3 I/O modules have been interconnected, you are now ready to connect power
to the DNP3 I/O modules. See “DNP3 I/O module (LV) connection to the Power Source” on
page 179.
First DNP I/O
Module
Second DNP I/O
Module
J1
To Field Equipment
To Field Equipment
J1
J2
J2
Daisy-chained
to other DNP I/O
Modules
Last DNP I/O
Module
To Field Equipment
J1
J2
Pin
1
4
5
6
7
Other
Function
GND
+DC1
-DC1
TX/RX2
TX/RX2
Not Used
To RTU Master
To Power Source
Standard Cables
DB9 male to
977-0089)
RTU Master
Cable
GE Part
Number
IP-Server
977-0503
Cable: GE Part Number
977-0500
J1
J2
DB9 male
(GE part number
Cable: D400 (RTU Master)
GE Part Number: 977-0503
To D400 (RTU Master)
To Field Equipment
To Field Equipment
To Field Equipment
To Power Source
J1
J2
J1
J2
J1
J2
Summary of Contents for Multilin D400
Page 12: ...12 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL PRODUCT SUPPORT ...
Page 28: ...28 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 34: ...34 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 2 INSTALLING THE D400 ...
Page 88: ...88 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 5 POWERING UP THE D400 ...
Page 174: ...174 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX A STANDARDS PROTECTION ...
Page 184: ...184 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX C LIST OF ACRONYMS ...
Page 192: ...192 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL INDEX ...