CHAPTER 6: SETTING UP THE D400
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
GE INFORMATION
95
Installing the certificate and key
Once you have obtained your security certificate and private key, you can install them on
the D400 in two ways:
•
Secure Copy - requires a PC with an installed Secure Copy Program (SCP) and a
network connection to the D400
•
USB Portable Memory Device - requires local access to the D400
Prerequisites
Before installing the certificate and key, check that the files are named as follows and
rename if necessary:
•
Certificate is
server.crt
•
Private key is
server.key
Procedures
To install using Secure Copy
1.
Start the Secure Copy Program.
2.
Connect to and log in to the D400 using your network connection.
3.
Using the Secure Copy Program, copy the
server.crt
and
server.key
files to the
following directory on the D400:
/mnt/usr/D400_SysConfig/Certificate
4.
Reboot the D400. See “Shutting down the D400” on page 112.
To install from the USB drive
1.
Copy the
server.crt
and
server.key
files to the root directory of the USB drive.
2.
Insert the USB drive into one of the front USB ports on the D400.
3.
Start a terminal session and log in to the D400.
4.
At the
D400#>>
command prompt, enter the following commands:
mkdir /mnt/usbdrive
mount -t vfat /dev/sda1 /mnt/usbdrive
cp /mnt/usbdrive/server.crt /mnt/usr/_SysConfig/Certificate
cp /mnt/usbdrive/server.key /mnt/usr/_SysConfig/Certificate
sync
umount /dev/sda1
5.
Remove the USB drive.
6.
Reboot the D400. See “Shutting down the D400” on page 112.
TIP
Since a USB drive could be lost or stolen, it is recommended you remove the private key
and certificate from the USB drive once you are done installing them on the D400.
Once you have installed and set up your security certificate, your secure Web access with
the D400 is enabled. From this point on, whenever you access the D400 HMI using a Web
browser, the D400 automatically sends you its Web site certificate, and your Web browser
displays a lock icon on the status bar. This indicates that you have a secure connection
with the D400.
NOTE
If you receive any other security warnings or do not see the secure connection icon in your
Web browser, your computer and network connection may not be safe from outside
intruders. Check with your IT administrator on how to proceed.
Summary of Contents for Multilin D400
Page 12: ...12 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL PRODUCT SUPPORT ...
Page 28: ...28 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 34: ...34 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 2 INSTALLING THE D400 ...
Page 88: ...88 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 5 POWERING UP THE D400 ...
Page 174: ...174 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX A STANDARDS PROTECTION ...
Page 184: ...184 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX C LIST OF ACRONYMS ...
Page 192: ...192 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL INDEX ...