CHAPTER 11: INTRODUCING THE D400 FEATURES
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
GE INFORMATION
131
Parallel Redundancy Protocol (PRP)
NOTE
Parallel Redundancy Protocol functionality is available with D400 firmware version 5.01.
The D400 provides the user with an option to Enable PRP on a per-VLAN basis.
The D400 simultaneously supports VLANs with PRP, and VLANs without PRP.
The D400 is able to communicate with the following LAN types:
•
IEDs with Dual LAN (two MACs, two IPs)
•
IEDs with Redundant LAN (single MAC, single IP)
•
IEDs on VLAN with PRP enabled
•
IEDs on VLAN without PRP enabled
The D400 supports PRP on the following network interface cards (NICs):
•
100BASEFX
•
4-Port Ethernet Switch
The following hardware is required to support PRP scenarios which require the third
Ethernet option:
•
D400 1.6GHz main board (520-0232LF)
•
Dual Ethernet kit
–
PC/104-PLUS 10/100/1000BASE-TX Dual Ethernet card (GE part number 580-
3410)*
–
Ethernet card to main board cable assemblies (GE part number 977-0544 and
977-0549)
•
Network card installed in the First network slot (Slot 11 - refer to Figure 6):
–
4-Port twisted-pair Ethernet switch (GE part number 520-0213LF refer to section:
“4-Port twisted-pair ethernet switch” on page 48),
OR
–
100Base-FX Hot Standby Fiber Optic Ethernet Adapter (GE part number 520-
0215LF refer to section: “100Base-FX hot standby fiber optic ethernet adapter” on
page 50).
•
Redundant twisted-pair Et COM2 port adapter (GE part number 520-0218LF
refer to page 52) network card installed in the Second Network slot (Slot 12 - refer to
Figure 6)
For details on PRP scenarios, refer to the D400 Online Help
Networking in D400
book >
Network LAN Scenarios
topic)
NOTE
PRP is not supported with the previous generation PC/104-Plus 10/100BaseT Ethernet
Module card (GE part number 580-2717). A replacement can be ordered from the D400
Upgrade Kits, available through the GE Grid Solutions Online store.
NOTE
NET 3 LEDs are not connected to the D400 Front panel LED cluster, but the NET 3 LINK
Good status can be monitored remotely from the System Status Manager - Digital Input
Points (refer to the D400 Online Help >
Application Pseudo Points
book >
System Status
Manager
topic).
Summary of Contents for Multilin D400
Page 12: ...12 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL PRODUCT SUPPORT ...
Page 28: ...28 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 34: ...34 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 2 INSTALLING THE D400 ...
Page 88: ...88 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 5 POWERING UP THE D400 ...
Page 174: ...174 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX A STANDARDS PROTECTION ...
Page 184: ...184 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX C LIST OF ACRONYMS ...
Page 192: ...192 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL INDEX ...