5-16
MIGII Digital Protection for Electrical Machines
GEK-113188A
5.3 ADVANCED SETTINGS
5 SETTINGS
5
5.3.6 PHASE IOC 50P
5.3.7 GROUND IOC 50G
PHASE IOC 50P
Delay 50P
Range: 0 – 600 s
Default: 0 s
Step: 0.1
PHASE IOC 50P
Trip enable 50P
ENTER
ADVANCED SETTINGS
PHASE IOC 50P
PHASE IOC 50P
Enable 50P
Range: Yes/No
Default: No
Range: Yes/No
Default: Yes
PHASE IOC 50P
Pickup 50P
Range: 0.1 – 30 FLC
Default: 0.5 FLC
Step: 0.1
ENTER
MENU
MAIN SETTINGS
ADVANCED
SETTINGS
PHASE IOC 50P
GROUND IOC 50G
Delay 50G
Range: 0 – 600 s
Default: 0 s
Step: 0.1
GROUND IOC 50G
Trip enable 50G
ENTER
ADVANCED SETTINGS
GROUND IOC 50G
GROUND IOC 50G
Enable 50G
Range: Yes/No
Default: No
Range: Yes/No
Default: Yes
GROUND IOC 50G
Pickup 50G
Range: 0.1 – 30 FLC
Default: 0.5 FLC
Step: 0.1
ENTER
MENU
MAIN SETTINGS
ADVANCED
SETTINGS
GROUNDIOC 50P