GEK-113188A
MIGII Digital Protection for Electrical Machines
5-19
5 SETTINGS
5.3 ADVANCED SETTINGS
5
5.3.10 F87R (MIGII P)
5.3.11 USER CURVE
ENERVISTA MII SETUP
HMI
DEFAULT
RANGE
STEP
Parameters
User Curve
User Curve
A
A Parameter
A Parameter
0.0500
0.0000-125.0000
0.0001
B
B Parameter
B Parameter
0.0000
0.0000-3.0000
0.0001
P
P Parameter
P Parameter
0.0400
0.0000-3.0000
0.0001
Q
Q Parameter
Q Parameter
1.0000
0.0000-2.0000
0.0001
K
K Parameter
K Parameter
0.000
0.000-1.999
0.001
F87R
Pickup 87R
Range: 0.05 – 0.3 In
Default: 0.1 In
Step: 0.01
F87R
Trip Enable 87R
ENTER
ADVANCED SETTINGS
F87R
F87R
Enable 87R
Range: Yes/No
Default: No
Range: Yes/No
Default: Yes
F87R
K87R
Range: 1 – 100%
Default: 10%
Step: 1%
F87R
Delay 87R
Range: 0 – 600 s
Default: 0.1
Step: 0.1
ENTER
MENU
MAIN SETTINGS
ADVANCED
SETTINGS
F87R