9 RELAY COMMISSIONING
9.13 GROUND IOC LOW SETTING ELEMENT (50G)
9
9.13GROUND IOC LOW SETTING ELEMENT (50G)
Enable only 50G element.
Set its time delay and pickup to the minimum possible
With 0.9 times the pickup current the relay should not trip.
With 1.1 times the pickup current the relay should trip in between 10 to 50 ms.