GEK-113188A
MIGII Digital Protection for Electrical Machines
9-17
9 RELAY COMMISSIONING
9.15 GROUND TOC ELEMENT (51G)
9
9.15.4 ANSI INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 36.2 and 51.3 sec.
Apply 5 times the pickup current and the relay should trip between 3.88 and 4.27 sec.
9.15.5 ANSI VERY INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 26.72 and 37.27 sec.
Apply 5 times the pickup current and the relay should trip between 2.46 and 2.75 sec.
9.15.6 ANSI EXTREMELY INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 17.19 and 23.58 sec.
Apply 5 times the pickup current and the relay should trip between 1.14 and 1.34 sec
9.15.7 DEFINITE TIME
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.1 times the pickup current and the relay should trip in 1.0 sec. Acceptable time range is between 1.00 and 1.06 sec.
Apply 4 times the pickup current and the relay should trip in 1.0 sec. Acceptable time range is between 1.00 and 1.06 sec.
51G SETTINGS GROUP
Curve
INVERSE
Time Dial
10
51G SETTINGS GROUP
Curve
VERY INVERSE
Time Dial
10
51G SETTINGS GROUP
Curve
EXTREMELY INVERSE
Time Dial
5
51G SETTINGS GROUP
Curve
DEFINITE TIME
Definite Time Delay
1.0