GEK-113188A
MIGII Digital Protection for Electrical Machines
C-15
APPENDIX C
C.7 MODBUS MAP - SETTINGS
C
INTEL
ADDRESS
MOTOROLA
ADDRESS
BITS
NAME
DESCRIPTION
# OF
BYTES
FORMAT
028C
0146
6
A50G
50G Pickup
2
BIT
028C
0146
8
A 49
49 Alarm
2
BIT
028C
0146
9
A 48
48 Pickup
2
BIT
028C
0146
10
A51P
51P Pickup
2
BIT
028C
0146
11
A51G
51G Pickup
2
BIT
028C
0146
14
A 46
46 Pickup
2
BIT
028E
0147
0
I E50P
50P Disable (by DI)
2
BIT
028E
0147
1
IE37
37 Disable (by DI)
2
BIT
028E
0147
2
I E50G
50G Disable (by DI)
2
BIT
028E
0147
6
I E49
49 disabled (by DI)
2
BIT
028E
0147
8
IE48
48 Disable (by DI)
2
BIT
028E
0147
9
I E51P
51P Disable (by DI)
2
BIT
028E
0147
10
I E51G
51G Disable (by DI)
2
BIT
028E
0147
11
I E66
66 Disable (by DI)
2
BIT
028E
0147
13
IE46
46 Disable (by DI)
2
BIT
028E
0147
14
D INH
Trip disabled (by DI)
2
BIT
028E
0147
15
D50p
50P Trip
2
BIT
0290
0148
0
D 37
37 Trip
2
BIT
0290
0148
1
D50g
50G Trip
2
BIT
0290
0148
2
D49
49 Trip
2
BIT
0290
0148
6
D 48
48 Trip
2
BIT
0290
0148
8
D51p
51P Trip
2
BIT
0290
0148
9
D51g
51G Trip
2
BIT
0290
0148
10
D ST
Stop Trip
2
BIT
0290
0148
11
D 66
66 Operation
2
BIT
0290
0148
12
D 46
46 Trip
2
BIT
0290
0148
13
DISGEN
General trip
2
BIT
Summary of Contents for Multilin MIGII