C-18
MIGII Digital Protection for Electrical Machines
GEK-113188A
C.8 MODBUS MAP- STATUS
APPENDIX C
C
INTEL
ADDRESS
MOTOROLA
ADDRESS
BITS
NAME
DESCRIPTION
# OF
BYTES
FORMAT
021
E
010F
Curve 46
46P Curve T2
2
ENUMERATION
0220
0110
TD Mult 46
46P K T2
4
FLOAT32
0224
0112
Delay 46
46P Time Delay T2
4
FLOAT32
0228
0114
Pickup 48
48 Pickup T2
4
FLOAT32
022C
0116
Delay 48
48 Time delay T2
4
FLOAT32
0230
0118
Block Delay 48
Block 48 from offline T2
4
FLOAT32
0234
011A
Pickup 49
Pickup 49 T2
4
FLOAT32
0238
011C
Alarm Level 49
Alarm Level 49 T2
4
FLOAT32
023C
011E
Heat Time 49
Heat Time 49 T2
4
FLOAT32
0240
0120
Cool Time 49
Cool Time 49 T2
4
FLOAT32
0244
0122
Constant K1
K1 T2
4
FLOAT32
0248
0124
Number of Starts
Starts per hour T2
4
FLOAT32
024C
0126
Time to Restart
Restart Time T2
4
FLOAT32
0250
0128
K 87R
87R K T2
4
FLOAT32
0254
012A
S 87R
87R S T2
4
FLOAT32
0258
012C
Delay 87R
87R Time Defined T2
4
FLOAT32
0270
0138
A Parameter
A Parameter
4
FLOAT32
0274
013A
B Parameter
B Parameter
4
FLOAT32
0278
013C
P Parameter
P Parameter
4
FLOAT32
027C
013E
Q Parameter
Q Parameter
4
FLOAT32
0280
0140
K Parameter
K Parameter
4
FLOAT32
0284
0142
0
O1
Oscillo by communic.
2
BIT
0284
0142
1
O2
Oscillo by digital input
2
BIT
0284
0142
2
O3
Oscillo by tripping
2
BIT
0284
0142
3
O4
Oscillo by pickup
2
BIT
0286
0143
0
sAPCOM
Trip operation by command
2
BIT
0286
0143
1
sRLATC
Reset latch aux
2
BIT
0286
0143
7
EMER
Emergency Restart
2
BIT
0286
0143
10
sC INT
Close Breaker operation
2
BIT
0288
0144
9
E PROT
Protection status
2
BIT
0288
0144
10
aux1
Output 1
2
BIT
0288
0144
11
aux2
Output 2
2
BIT
0288
0144
12
aux3
Output 3
2
BIT
0288
0144
13
aux4
Output 4
2
BIT
0288
0144
14
ENT1
Digital Input 1
2
BIT
0288
0144
15
ENT2
Digital Input 2
2
BIT
028A
0145
1
ihca
Sett. change disable
2
BIT
028A
0145
2
ORD D
Trip operation by input
2
BIT
028A
0145
4
ED 52B
Breaker 52B
2
BIT
028A
0145
6
C TAB
Settings group change
2
BIT
028A
0145
7
Gosc
Oscillo trigg by DI
2
BIT
028A
0145
9
est INTE
Breaker Closed
2
BIT
028A
0145
10
STOC
Oscillo trigg by comm
2
BIT
028A
0145
13
SMAR
Motor Running
2
BIT
028A
0145
14
C AJUS
Settings change
2
BIT
028A
0145
15
SE2P
EEPROM Failure
2
BIT
028C
0146
0
Adef
User settings
2
BIT
028C
0146
1
A50P
50P Pickup
2
BIT
028C
0146
2
A 37
37 Pickup
2
BIT
Summary of Contents for Multilin MIGII
Page 2: ......