GEK-113188
MIGII Digital Protection for Electrical Machines
E-7
APPENDIX E
E.3 SAMPLES OF SETTINGS FOR PARTICULAR MODEMS
E
Set 3
Location of modem microswitches on the RELAY side:
Set 1
NO
DESCRIPTIONº
VALUE
1&2
Transmission timer selection.
ON-ON114
OFF-ON113
ON-OFF114/5
OFF-OFF113
ON-ON
3
RTC Dialing system
ON: Multi-frequency dialing.
OFF: Loop opening pulse dialing
ON
4
Status of circuit 109, during protocol V.25bis in RTC, option 108.2.
ON: Status of circuit 108 remains.
OFF: Remains open.
OFF
5
Selection, when starting, of manual or automatic answering mode.
ON: Automatic.
OFF: Manual.
OFF
6
Protocol selection.
ON: HAYES Protocol.
OFF: V.25bis Protocol.
OFF
7&8
Modem transmission level.
ON-ON-6 dBm
OFF-ON-10 dBm
ON-OFF-6 dBm
OFF-OFF-15 dBm
ON-ON
Nº
DESCRIPTIÓN
VALUE
1
112 ETD/OFF
ON: Circuit 112 connected to ETD
OFF: Circuit 112 connected to ETD
ON
2
112 ETD/ON
ON: 108 circuit forced to CLOSED.
OFF: 108 circuit follows ETD’s 108 circuit
ON
3
105 ETD/ON
ON: Circuit 105 forced to CLOSED.
OFF: Circuit 105 follows ETD’s 105circuit
ON
4
TXA/TXB in a peer-to-peer line (PP)
ON: In PP transfers through high channel.
OFF: In PP transfers through low channel.
ON
5&6
Baud rate selection for data transfer.
ON-ON1200
OFF-ON2400
ON-OFFAutomatic.
OFF-OFFAutomatic.
ON-OFF
7&8
Automatic disconnection.
ON-ONNo automatic disconnection.
OFF-ONCircuit 105.
ON-OFFCircuit 109.
OFF-OFFCircuits 105 and 109.
OFF-OFF
Summary of Contents for Multilin MIGII
Page 2: ......