GEK-113188A
MIGII Digital Protection for Electrical Machines
5-5
5 SETTINGS
5.2 MAIN SETTINGS
5
5.2.3 LOCKED ROTOR 48 (MIGII Q)
LOCKED ROTOR 48
Delay 48
LOCKED ROTOR 48
Block Delay 48
Range: 0 – 600 s
Default: 0 s
Range: 1 – 900 s
Default: 0 s
LOCKED ROTOR 48
Trip enable 48
ENTER
MENU
MAIN SETTINGS
LOCKED ROTOR
48
ENTER
MAIN SETTINGS
LOCKED ROTOR 48
LOCKED ROTOR 48
Enable 48
Range: Yes/No
Default: No
Range: Yes/No
Default: Yes
LOCKED ROTOR 48
Pickup 48
Range: 1.01 - 10 FLC
Default: 1.01 FLC
Step: 0.01
Summary of Contents for Multilin MIGII