MIGII Digital Protection for Electrical Machines
GEK-113188A
5.2 MAIN SETTINGS
5 SETTINGS
5
5.2.9 NUMBER OF STARTS 66
5.2.10 F87R (MIGII P)
NUMBER STARTS 66
Time to restart
Range: 0 – 10 min
Default: 10 min
Step: 1min
NUMBER STARTS 66
Operate 66
ENTER
MENU
MAIN SETTINGS
NUMBER STARTS
66
ENTER
MAIN SETTINGS
NUMBER STARTS 66
NUMBER STARTS 66
Enable 66
Range: Yes/No
Default: No
Range: Yes/No
Default: Yes
NUMBER STARTS 66
Number of starts
Range: 1 – 10
Default: 5
Step: 1
F87R
Pickup 87R
Range: 0.05 – 0.3 In
Default: 0.1 In
Step: 0.01
F87R
Trip Enable 87R
ENTER
MAIN SETTINGS
F87R
F87R
Enable 87R
Range: Yes/No
Default: No
Range: Yes/No
Default: Yes
F87R
K87R
Range: 1 – 100%
Default: 10%
Step: 1%
F87R
Delay 87R
Range: 0 – 600 s
Default: 0.1
Step: 0.1
ENTER
MENU
MAIN SETTINGS
F87R