GEK-113188A
MIGII Digital Protection for Electrical Machines
5-11
5 SETTINGS
5.3 ADVANCED SETTINGS
5
5.3ADVANCED SETTINGS
5.3.1
NOTE ABOUT THE TRIP MIN TIME SETTING:
This setting indicates the time during which the tripping contact will remain closed as a minimum in
case of fault. If the fault persists for a longer time than the set value, the tripping contact will remain
closed and will be opened immediately after the fault is cleared, while if the fault is shorter than the
set time, the relay will maintain the contact closed for this set time.
MENU
MAIN SETTINGS
ADVANCED SETTINGS
ENTER
ADVANCED SETTINGS
GENERAL ADVANCED
GENERAL ADVANCED
Setting Group
GENERAL ADVANCED
Trip Min Time
Range: 1 - 2
Default: 1
Range: 50-300 ms
Default: 200 ms