5-22
MIGII Digital Protection for Electrical Machines
GEK-113188A
5.3 ADVANCED SETTINGS
5 SETTINGS
5
5.3.13 OSCILLOGRAPHY MASKS
5.3.14 MIGII INTERNAL STATUSES
COMMENTS ON SETTINGS:
The factory default HMI password to change any setting is 1. See Chapter 8 for details.
The ACTIVE GROUP setting, in the Advanced General Settings, selects which of the two settings groups is active at a
given time. Its default value is 1 (GROUP 1).
The procedure to set the Phase and Ground TOC (Time Delayed Overcurrent) functions (51P / 51N) is the same for both
functions: First, the pickup value must be set (PICKUP); Then, using the CURVE TYPE (current versus time tripping
characteristic curve), the type of time delay preferred is selected, either DEFINITE TIME, or any of the three inverse
curves; If the choice is any of the inverse curves (Inverse, Very Inverse or Extremely Inverse), then the relay takes into
account the TIME DIAL setting, to identify which of the curves in the family must be used (there are 195 different curves
for each curve type, depending on the Time Dial Selected); if the curve type selected is DEFINITE TIME, then the Time
Dial setting is ignored and the time delay used is the one specified in DEFINITE TIME setting.
OSCILLOGRAPHY MASK
ENERVISTA MII SETUP
DEFAULT
RANGE
STEP
Oscillography masks
Oscillography mask
Oscillo by communications
Oscillo by communic.
NO
Y/N
NA
Oscillo by digital input
Oscillo by Digital Input
NO
Y/N
NA
Oscillo by trip
Oscillo by trip
NO
Y/N
NA
Oscillo by pickup
Oscillo by pickup
NO
Y/N
NA
STATUS
STATUS
STATUS
Model
Pickup 51P-C
Trip 87R
Version
Pickup 37
Trip 46
Date - Time
Pickup 48
Trip 49
Identification
Pickup 50P
Trip by stop
Ia
Pickup 50G
Operation 66
Ib
Pickup 51P
Alarm
Ic
Pickup 51G
Trip
Ig
Pickup 46
Output 1
I1
Alarm 49
Output 2
I2
General Pickup
Output 3
Id
Trip 37-A
Output 4
Thermal Image (Th)
Trip 37-B
Input 1
Number of Starts
Trip 37-C
Input 2
Time to restarts
Trip 48-A
READY
Oscillo number
Trip 48-B
Trip LED
Event number
Trip 48-C
LED 1
Active table
Trip 50P-A
LED 2
Frequency
Trip 50P-B
LED 3
Pickup 37-A
Trip 50P-C
LED 4
Pickup 37-B
Trip 51P-A
Logic 1
Pickup 37-C
Trip 51P-B
Logic 2
Pickup 48-A
Trip 51P-C
Logic 3
Pickup 48-B
Trip 37
Logic 4
Pickup 48-C
Trip 48
Table Change
Pickup 50P-A
Trip 50P
Settings change inhibition
Pickup 50P-B
Trip 50G
52 Closed
Pickup 50P-C
Trip 51P
Started motor
Pickup 51P-A
Trip 51G
EEPROM Failure
Pickup 51P-B
Trip 87R
User settings