9-30
MIGII Digital Protection for Electrical Machines
GEK-113188A
9.24 ADVANCED SETTINGS
9 RELAY COMMISSIONING
9
9.24ADVANCED SETTINGS
9.24.1 GENERAL SETTINGS
9.24.2 PHASE / GROUND TOC SETTINGS (51P / 51G) (TABLE 2)
9.24.3 PHASE / GROUND IOC SETTINGS (50P / 50G) (TABLE 2)
ENERVISTA MII PC
HMI
VALUE RANGE
STEP
GENERAL ADVANCED
SETTINGS
GENERAL
ADVANCED
SETTINGS
GENERAL ADVANCED
Identification
IDENTIFICATION
---
Text
NA
Active Table
ACTIVE TABLE
Active Group
1-2
NA
Minimum tripping time
MIN TRIP TIME
Trip Min Time
50-300 ms
1 ms
ENERVISTA MII PC
HMI
VALUE
RANGE
STEP
Phase TOC Function Table 2
51P Function T2
PHASE TOC
51P
51P Enable Table 2
Enable
T2
Enable
51P
Y/N
NA
51P Permission to Trip Table 2
51P Trip Permission
T2 Trip Enable 51P
Y/N
NA
51P Tap / Pickup Value Table 2
51P Pickup
T2
Pickup 51P
0.1-2.4 FLA (Ph)
0.01
51P Curve Type Table 2
51P Curve Type
Curve 51P
INV, V.I., E.I., T.DE, USU
NA
51P Time Dial Table 2
51P Time Dial
T2
TD Mult 51P
0.05 - 2.00 (IEC curves)
0.01
0.5 - 20.0 (ANSI curves)
0.01
51P Definite Time Delay Table 2
51P Definite Time
T2
Def Time 51P
0 - 600 s.
0.01 s.
Ground TOC Function Table 2
51G Function
F51G
51G Enable Table 2
Enable
T2
Enable
51G
Y/N
NA
51G Permission to Trip Table 2
51G Trip Permission
T2 Trip Enable 51G
Y/N
NA
51G Tap / Pickup Table 2
51G Pickup
T2
Pickup 51G
0.1 - 2.4 In (Gnd)
0.01 In (Gnd)
51G Curve Type Table 2
51G Curve Type
T2
Curve 51G
INV, V.I., E.I., T.DE, USU
NA
51G Time Dial Table 2
51G Time Dial
T2
TD Mult 51G
0.05 - 2.00 (IEC curves)
0.01
51G Definite Time Delay Table 2
51G Definite Time
T2
Def Time 51G
0 - 600 s.
0.01 s.
ENERVISTA MII PC
HMI
VALUE RANGE
STEP
Phase IOC Setting Table 2
50P Function T2
PHASE TOC 50P
50P Enabling Table 2
Enable
T2
Enable
50P
Y/N
NA
50P Permission to Trip Table 2
50P Trip Permission
T2
Trip Enable 50P
Y/N
NA
50P Tap / Pickup Table 2
50P Pickup
T2
Pickup 50P
0.1 - 30 FLA
0.1
50P Time Delay Table 2
50P Time Delay
T2
Delay 50P
0 - 600 s.
0.01 s.
Ground IOC Setting Table 2
50G Function T2
GROUND IOC 50G
50G Enabling Table 2
Enable
T2
Enable
50G
Y/N
NA
50G Permission to Trip Table 2
50G Trip Permission
T2
Trip Enable 50G
Y/N
NA
50G Tap / PickupTable 2
50G Pickup
T2
Pickup 50G
0.1 - 30 In (Gnd)
0.1 In (G)
50G Time Delay Table 2
50G Time Delay
T2
Delay 50G
0 - 600 s.
0.01 s.