GEK-113188A
MIGII Digital Protection for Electrical Machines
5-9
5 SETTINGS
5.2 MAIN SETTINGS
5
5.2.8 GROUND TOC 51G
GROUND TOC 51P
Curve 51P
Range: Extr. Inverse/ Definite Time/ User/
Mod Inverse/ Very Inverse
Default: Definite Time
GROUND TOC 51P
Trip enable 51P
ENTER
MENU
MAIN SETTINGS
GROUND TOC
51P
ENTER
MAIN SETTINGS
GROUND TOC 51P
GROUND TOC 51P
Enable 51P
Range: Yes/No
Default: No
Range: Yes/No
Default: Yes
GROUND TOC 51P
Pickup 51P
Range: 0.1 – 2.4 In
Default: 0.5 In
Step: 0.1
GROUND TOC 51P
TD Mult 51P
Range: 0.05 – 2 (IEC) or 0.5 – 20 (ANSI)
Default: 0.5 (IEC) or 5 (ANSI)
Step: 0.01
GROUND TOC 51P
Def Time 51P
Range: 0 – 600 s
Default: 1 s
Step: 0.1