GEK-113308
MIWII Directional Power Protection System
2-23
2 PRODUCT DESCRIPTION
2.13 TECHNICAL SPECIFICATIONS
2
2.13.5 OUTPUTS
Max. Ratings for 100.000 operations:
2.13.6 COMMUNICATIONS
2.13.5.1 TRIPPING CONTACTS
Contact capacity:
Maximum operation voltage
440 Vac
Continuous :
16 A at 250 Vac, general purpose
¾ HP, 124 Vac
1-1/2 HP, 250 Vac
10 A, 250 Vac, 0.4 F.P.
B300 pilot duty
Make and Carry:
48 A
Breaking capacity:
4000 VA
2.13.5.2 OUTPUT RELAYS
Configuration:
6 Electro-Mechanical Form C
Contact Material:
Silver alloy suited for inductive loads
VOLTAGE
MAKE&CARRY
CONTINUOUS
MAKE&CARRY 0.2 SEC
BREAK
MAX LOAD
DC Resistive
24 Vdc
16 A
48 A
16 A
384W
48 Vdc
16 A
48 A
2.6 A
125W
125 Vdc
16 A
48 A
0.6 A
75 W
250 Vdc
16 A
48 A
0.5 A
125 W
AC Resistive
120 Vac
16 A
48 A
16 A
1920 VA
250 Vac
16 A
48 A
16 A
4000 VA
AC Inductive
PF = 0.4
250 Vac
10 A
30 A
10 A
1000 VA
FRONT PORT
RS232
300, 600, 1200, 2400, 4800, 9600 or 19200 bps,
Modbus® RTU
REAR PORT
RS485
300, 600, 1200, 2400, 4800, 9600 or 19200 bps,
Modbus® RTU