CHAPTER 3: ENERVISTA MULTINET4 SETUP SOFTWARE
ENERVISTA MULTINET4 SETUP SOFTWARE
MULTINET4 MULTI-PORT SERIAL SERVER & MANAGED SWITCH – INSTRUCTION MANUAL
3–13
files for a previously created EnerVista Multinet4 Setup file with the extension XML as the
desired target. If no settings files have been previously created, then create a Settings List
File.
Once a Target or Disk settings file has been selected to receive the Multinet4 device’s
settings, click the
Receive
button. The EnerVista Multinet4 Setup program will read the
settings of the Multinet4 and store them in the selected target settings file.
3.9.2
Writing Settings to a Device
Before writing to a Multinet4 device is possible, a settings file (*.xml) must be created, or an
existing settings file must be selected from the Settings List tree directory.
To Write a Settings File to a Device:
Z
Choose a desired settings file from the Setting List directory under
Offline windows.
Z
Select
Write Settings to Device
either from the menu of main
window or right click Mouse on the desired settings file in the Off-
Line Window
Z
Select
Write Settings to Device
from the Settings List Pop-Up
Menu
A
Select Target Device
window will appear.
Z
Select the desired target device.
Z
Click
Send
.
The EnerVista Multinet4 Setup program will now download the
ENTIRE selected Settings file to the selected Multinet4 Target
Device.
If your Multinet4 device is On-line and successfully communicating, all previously stored,
device settings will be overwritten once the Send button is clicked.
If IP address is modified, you have to re-configure the online device using the Device Setup
feature.