B-40
N60 Network Stability and Synchrophasor Measurement System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
AB25
Command to clear XCBR1 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB26
Operand for IEC 61850 XCBR2.ST.Loc status
0 to 65535
---
1
F300
0
AB27
Command to clear XCBR2 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB28
Operand for IEC 61850 XCBR3.ST.Loc status
0 to 65535
---
1
F300
0
AB29
Command to clear XCBR3 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB2A
Operand for IEC 61850 XCBR4.ST.Loc status
0 to 65535
---
1
F300
0
AB2B
Command to clear XCBR4 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB2C
Operand for IEC 61850 XCBR5.ST.Loc status
0 to 65535
---
1
F300
0
AB2D
Command to clear XCBR5 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB2E
Operand for IEC 61850 XCBR6.ST.Loc status
0 to 65535
---
1
F300
0
AB2F
Command to clear XCBR6 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
IEC 61850 LN name prefixes (read/write settings)
AB30
IEC 61850 logical node LPHD1 name prefix
0 to 65534
---
1
F206
(none)
AB33
IEC 61850 logical node PIOCx name prefix (72 items)
0 to 65534
---
1
F206
(none)
AC0B
IEC 61850 logical node PTOCx name prefix (24 items)
0 to 65534
---
1
F206
(none)
AC53
IEC 61850 logical node PTUVx name prefix (13 items)
0 to 65534
---
1
F206
(none)
AC7A
IEC 61850 logical node PTOVx name prefix (10 items)
0 to 65534
---
1
F206
(none)
AC98
IEC 61850 logical node PDISx name prefix (10 items)
0 to 65534
---
1
F206
(none)
ACB6
IEC 61850 logical node RBRFx name prefix (24 items)
0 to 65534
---
1
F206
(none)
ACFE
IEC 61850 logical node RPSBx name prefix
0 to 65534
---
1
F206
(none)
AD01
IEC 61850 logical node RRECx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD13
IEC 61850 logical node MMXUx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD25
IEC 61850 logical node GGIOx name prefix (4 items)
0 to 65534
---
1
F206
(none)
AD31
IEC 61850 logical node RFLOx name prefix (5 items)
0 to 65534
---
1
F206
(none)
AD40
IEC 61850 logical node XCBRx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD52
IEC 61850 logical node PTRCx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD64
IEC 61850 logical node PDIFx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD70
IEC 61850 logical node MMXNx name prefix (6 items)
0 to 65534
---
1
F206
(none)
IEC 61850 GGIO4 general analog configuration settings (read/write)
AF00
Number of analog points in GGIO4
4 to 32
---
4
F001
4
AF01
GOOSE analog scan period
100 to 5000
---
10
F001
1000
IEC 61850 GGIO4 analog input points configuration settings (read/write)
AF10
IEC 61850 GGIO4 analog input 1 value
---
---
---
F600
0
AF11
IEC 61850 GGIO4 analog input 1 deadband
0.001 to 100
%
0.001
F003
100000
AF13
IEC 61850 GGIO4 analog input 1 minimum
–1000000000000 to
1000000000000
---
0.001
F060
0
AF15
IEC 61850 GGIO4 analog input 1 maximum
–1000000000000 to
1000000000000
---
0.001
F060
1000000
AF17
...Repeated for IEC 61850 GGIO4 analog input 2
AF1E
...Repeated for IEC 61850 GGIO4 analog input 3
AF25
...Repeated for IEC 61850 GGIO4 analog input 4
AF2C
...Repeated for IEC 61850 GGIO4 analog input 5
AF33
...Repeated for IEC 61850 GGIO4 analog input 6
AF3A
...Repeated for IEC 61850 GGIO4 analog input 7
AF41
...Repeated for IEC 61850 GGIO4 analog input 8
AF48
...Repeated for IEC 61850 GGIO4 analog input 9
AF4F
...Repeated for IEC 61850 GGIO4 analog input 10
AF56
...Repeated for IEC 61850 GGIO4 analog input 11
AF5D
...Repeated for IEC 61850 GGIO4 analog input 12
AF64
...Repeated for IEC 61850 GGIO4 analog input 13
AF6B
...Repeated for IEC 61850 GGIO4 analog input 14
AF72
...Repeated for IEC 61850 GGIO4 analog input 15
AF79
...Repeated for IEC 61850 GGIO4 analog input 16
AF80
...Repeated for IEC 61850 GGIO4 analog input 17
AF87
...Repeated for IEC 61850 GGIO4 analog input 18
Table B–9: MODBUS MEMORY MAP (Sheet 33 of 54)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT