NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy 

g

NetPro 3000/4000 only:

One of the applicance outlets (4a, fig. 1) is programmable. Three settings are possible:

!

ON

!

OFF

!

AUTO

When the UPS is started the outlet is always switched ON, but it can be switched off either manually or
automatically.
With the default setting 'ON', the outlet functions similar to the other appliance outlets: it delivers output
power as long as the output converter does. When 'OFF' is selected, the outlet switches off. When the
option 'AUTO' is selected, the system asks for the 'Off autonomy time': the remaining runtime (in minutes)
at which, during a mains failure, the programmable output is automatically switched off until the mains
returns. This way less critical equipment (e.g. screens, printer) can be switched off automatically in order
to lengthen the remaining runtime.
Figure 6 shows an example. The total predicted runtime is 15 minutes, and the 'off autonomy time' has
been set on 5 minutes: the outlet switches off 5 minutes before the predicted end of autonomy.

As the load decreases when the outlet switches
off, the actual remaining autonomy at the 'outlet
off' moment (which was predicted at present
load) will be longer than the programmed 5-
minute period.
In configurations with small loads and large
battery capacities, i.e. very long runtimes, the
step size with which the runtime is counted
down can be longer than the programmed 'off
autonomy time' (see section 3.5). In this case
the programmable outlet will be switched off
when the remaining runtime is one step from
zero.

Example: suppose the runtime is counted down with 10 minute steps, and the 'off autonomy time' is set
as mentioned above. Despite of the 5-minute setting, the outlet will be switched off 10 minutes (= one
step) before end of autonomy.
If the step size does not exceed the 'off autonomy time', the programmable outlet will be switched off at
the programmed moment although the accuracies may not match. Example: 'off autonomy time' set at 14
minutes while the step size is 10 minutes, the outlet will indeed be switched off 14 minutes before the end
of the autonomy.
If the option 'AUTO' is selected the programmable outlet can still be switched off manually using the front
panel keys.
Each time the mains returns, the programmable outlet will always be switched on. Therefore do not use
this outlet to switch off equipment that should permanently remain off.

The frequency tracking rate is the maximum rate at which the UPS adjusts its output frequency to
fluctuations of the input frequency. If the UPS is not connected to a generator set the default setting may
be too high. Note that a change of the frequency tracking 

rate

 is coupled with a change of the tracking

range

 (see chapter 8, bypass).

The runtime, below which the UPS is inhibited to start up, can be set here. The UPS will first recharge its
batteries and start up as soon as the 'start up autonomy' is available. The setting can be bypassed (see
also 3.2.3). Calculation of the 'start up autonomy' is based on the assumption that the UPS supplies 100%
load.

:BFI-'FJA=>A

PB-AB@KN67I'B@A>

(A@BA'@JAF7-A65>

15

0

5

mains

failure

remaining autonomy (minutes)

output

off

end of

autonomy

'Off 

autonomy

 time'

I4D211-9

fig. 6  Off autonomy time

Summary of Contents for NetPro Series

Page 1: ...nufactured by GE Digital Energy General Electric Company Telephone 41 0 91 850 51 51 CH 6595 Riazzino Locarno Fax 41 0 91 850 51 44 Switzerland Website www gedigitalenergy com GE Digital Energy Techno...

Page 2: ...2 Normal operation indications 3 3 3 Auto off no load shutdown 3 3 4 Automatic bypass switch 3 3 5 Switching off 3 4 Use Screen Menus 3 4 1 Default menu 3 4 2 Status messages and alarm messages 3 4 2...

Page 3: ...D ROM and this manual Inspect the UPS for damage after unpacking If any damage is present please immediately notify the carrier and place of purchase IMPORTANT Before making any connection and switchi...

Page 4: ...y pack 9 fig 1 4 to the DC socket of the UPS 7 fig 1 4 You will hear a click when the cable is properly installed Block the DC connector install the small locking plate 9a fig 4 that came with the bat...

Page 5: ...orking wall outlet the battery charger is active the batteries are being charged 2 Switch on the UPS with the on off switch 12 fig 1 at the rear of the unit the green LED operation will illuminate 3 T...

Page 6: ...S will switch off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will automatically turn on again when...

Page 7: ...e RMS input voltage 12 time until sleep in minutes if activated 23min the calculated available runtime at present load The calculation is based on two figures the capacity of the battery set and the e...

Page 8: ...only after the default screen is displayed again In case of weak mains the yellow LED 16 on the front panel illuminates and the buzzer remains silent high priority alarms indicate situations in which...

Page 9: ...ee section 6 2 Perhaps the replace battery alarm occurs after a manual test which you started immediately after installation or after a power failure In this case the alarm may be incorrect as the bat...

Page 10: ...is inhibited due to voltage or frequency errors of the mains supply or if the bypass function has been disabled see 3 4 3 the UPS may automatically switch off within a few seconds load dependent Outp...

Page 11: ...and stored with OK 19 If a setting is stored and will disappear One of the default screens will appear after 20 seconds of no key activity Blocking settings Pressing OK 19 and 18 simultaneously in a...

Page 12: ...tched off when the remaining runtime is one step from zero Example suppose the runtime is counted down with 10 minute steps and the off autonomy time is set as mentioned above Despite of the 5 minute...

Page 13: ...s supplied by a generator set and the generator s frequency is often out of the UPS s input tolerances frequently occurring bypass error alarms see 3 4 2 2 will be the result During these alarms bypas...

Page 14: ...untdown occurs with steps of 20 minutes each and during the last 20 minutes before the batteries are empty the runtime will be displayed as 20 min 3 6 Other Features 3 6 1 Shutdown Using communication...

Page 15: ...refer to the manual of your interface package or via the front panel with the push buttons OK and The procedure is as follows From a default screen press push button 20 until the display shows If no...

Page 16: ...n In order to keep track of the capacity deterioration due to aging of the batteries we advise to perform a battery calibration test at least once per year During a battery calibration test the batter...

Page 17: ...eed due to other circumstances than already indicated by pin 6 7 9 Output converter overload Overtemperature pre alarm Battery failure Fan failure High charger voltage Bypass out of limits Inverter sh...

Page 18: ...PowerFLAG SerVICe Box for Modem Connection If you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem a programmed number can be dialed in case of a UPS alarm It a...

Page 19: ...mperature See 3 4 2 3 Allow the UPS to cool down Line cord not connected Read 2 2 Connect line cord Batteries not connected Contact your dealer or consult www gedigitalenergy com Dead wall socket outl...

Page 20: ...1 msec Overload capability The UPS is fully protected against overload Overload behaviour on line operation bypass enabled 110 during 5 minutes 150 during 2 seconds on line operation bypass disabled...

Reviews: