NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy 

g

3.5

Runtime: calculation and indication

The available runtime is displayed in the default screen, and is counted down during battery operation
until either the mains returns or the batteries are empty.

Normally, i.e. if the runtime is less than 100 minutes, the runtime is calculated in minutes, and the step
size of the changes is one minute. In case of small loads and/or battery extension packs the available
runtime can be substantially longer. The accuracy of the runtime calculations however is limited: approx
1% of the initial runtime.
For this reason the measuring unit and step size will change at longer runtimes: if for example the runtime
is between 200 and 500 minutes the step size is 5 minutes; if the runtime is > 5000 minutes the runtime is
calculated in hours and the step size is 2 hrs. The following table gives an overview:

Runtime R

t

, in minutes

  Unit

  Step size

  R

t

 < 100

  minutes

  1 minute

  100 

 R

t

 < 200

  minutes

  2 minutes

  200 

 R

t

 < 500

  minutes

  5 minutes

  500 

 R

t

 < 1000

  minutes

 10 minutes

  1000 

 R

t

 < 2000

  minutes

 20 minutes

  2000 

 R

t

 < 5000

  hours

  1 hr

  R

t

 

 5000

  hours

  2 hrs

Please note that 

unit and step size do not change during countdown

: the initial units and step sizes

remain unaltered, until eventually the batteries are empty.
If during battery operation the available runtime becomes less than the step size it will be shown as '< S',
where S is the step size. If for example the initial autonomy was 1200 minutes, i.e. between 1000 and
2000, the countdown occurs with steps of 20 minutes each, and during the last 20 minutes before the
batteries are empty the runtime will be displayed as '< 20 min'.

3.6

Other Features

3.6.1 Shutdown

Using communication capabilities, the computer can direct the UPS to turn itself off following controlled
shutdown of the system. Subsequently the UPS will remain off for at least 30 seconds. LED '

operation

' will

go out. The unit will start up again as soon as the mains returns (and, if activated, the start-up runitme is
available).

3.6.2 Programmed shutdown

The UPS monitoring software allows you to program a 'sleep period' of the UPS by sending two
commands to the UPS:

-

shut down after # minutes, and subsequently:

-

shut down during # hours.

The first command indicates the period of time after which the UPS should 'fall asleep', the second
indicates the duration of the sleep period. After the first command LED 

'prog shutdown'

 starts blinking and

the standard screen shows the time until sleep (see 3.4.1). In the 'sleep'-mode LED 'operation' is off, LED
'progr. shutdown' is on, and the LCD shows the remaining sleep time:

During the 'sleep period' the UPS is not completely switched off as it has to keep track of the remaining
sleep time. However, if a mains failure occurs during the sleep period and the battery capacity eventually
drops below 80% of the normal capacity, the UPS will automatically switch off in order to save battery
power. When the mains returns the UPS will start up automatically (as soon as the start-up runtime is
available, if this feature is activated). The programmed sleep time however is lost.

The programmed shutdown in progress can be cancelled: press the OK button during 10 seconds to
cancel shutdown and switch the UPS on.

#65>'J7A6='O@N>_
SS_``_((

Summary of Contents for NetPro Series

Page 1: ...nufactured by GE Digital Energy General Electric Company Telephone 41 0 91 850 51 51 CH 6595 Riazzino Locarno Fax 41 0 91 850 51 44 Switzerland Website www gedigitalenergy com GE Digital Energy Techno...

Page 2: ...2 Normal operation indications 3 3 3 Auto off no load shutdown 3 3 4 Automatic bypass switch 3 3 5 Switching off 3 4 Use Screen Menus 3 4 1 Default menu 3 4 2 Status messages and alarm messages 3 4 2...

Page 3: ...D ROM and this manual Inspect the UPS for damage after unpacking If any damage is present please immediately notify the carrier and place of purchase IMPORTANT Before making any connection and switchi...

Page 4: ...y pack 9 fig 1 4 to the DC socket of the UPS 7 fig 1 4 You will hear a click when the cable is properly installed Block the DC connector install the small locking plate 9a fig 4 that came with the bat...

Page 5: ...orking wall outlet the battery charger is active the batteries are being charged 2 Switch on the UPS with the on off switch 12 fig 1 at the rear of the unit the green LED operation will illuminate 3 T...

Page 6: ...S will switch off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will automatically turn on again when...

Page 7: ...e RMS input voltage 12 time until sleep in minutes if activated 23min the calculated available runtime at present load The calculation is based on two figures the capacity of the battery set and the e...

Page 8: ...only after the default screen is displayed again In case of weak mains the yellow LED 16 on the front panel illuminates and the buzzer remains silent high priority alarms indicate situations in which...

Page 9: ...ee section 6 2 Perhaps the replace battery alarm occurs after a manual test which you started immediately after installation or after a power failure In this case the alarm may be incorrect as the bat...

Page 10: ...is inhibited due to voltage or frequency errors of the mains supply or if the bypass function has been disabled see 3 4 3 the UPS may automatically switch off within a few seconds load dependent Outp...

Page 11: ...and stored with OK 19 If a setting is stored and will disappear One of the default screens will appear after 20 seconds of no key activity Blocking settings Pressing OK 19 and 18 simultaneously in a...

Page 12: ...tched off when the remaining runtime is one step from zero Example suppose the runtime is counted down with 10 minute steps and the off autonomy time is set as mentioned above Despite of the 5 minute...

Page 13: ...s supplied by a generator set and the generator s frequency is often out of the UPS s input tolerances frequently occurring bypass error alarms see 3 4 2 2 will be the result During these alarms bypas...

Page 14: ...untdown occurs with steps of 20 minutes each and during the last 20 minutes before the batteries are empty the runtime will be displayed as 20 min 3 6 Other Features 3 6 1 Shutdown Using communication...

Page 15: ...refer to the manual of your interface package or via the front panel with the push buttons OK and The procedure is as follows From a default screen press push button 20 until the display shows If no...

Page 16: ...n In order to keep track of the capacity deterioration due to aging of the batteries we advise to perform a battery calibration test at least once per year During a battery calibration test the batter...

Page 17: ...eed due to other circumstances than already indicated by pin 6 7 9 Output converter overload Overtemperature pre alarm Battery failure Fan failure High charger voltage Bypass out of limits Inverter sh...

Page 18: ...PowerFLAG SerVICe Box for Modem Connection If you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem a programmed number can be dialed in case of a UPS alarm It a...

Page 19: ...mperature See 3 4 2 3 Allow the UPS to cool down Line cord not connected Read 2 2 Connect line cord Batteries not connected Contact your dealer or consult www gedigitalenergy com Dead wall socket outl...

Page 20: ...1 msec Overload capability The UPS is fully protected against overload Overload behaviour on line operation bypass enabled 110 during 5 minutes 150 during 2 seconds on line operation bypass disabled...

Reviews: