background image

OPM_NPE_XXX_2K0_4K0_1GB_V040

16

NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy 

g

4.1

RS232 Port (fig. 7)

The RS 232 Port is a plug-in interface port (9-pin, Sub-D, male) which enables advanced communication
between the UPS and the computer (UPS software required). The interface port is operative as soon as
the mains power cord is plugged into a live wall outlet, even if the UPS is switched off.
We strongly recommend to use only original GE Digital Energy software products in combination with
the interface port.

Pin #

Function

  1

RS232 input (UPS shutdown)

  2

RS232 output

  3

General alarm

1)

  4

Plug and Play

  5

Common

  6

Bypass active

  7

Battery low

  8

UPS connected

  9

Mains failure

1)

Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than
already indicated by pin 6-7-9:

-

 

Output converter overload

-

 Overtemperature 

(pre-)alarm

-

 Battery 

failure

-

 Fan 

failure

-

 

High charger voltage

-

 

Bypass out of limits

-

 

Inverter shutdown (due to inverter failure or batt. failure)

4.2

Relay Interface Card (option)

The card is equipped with potential free change-over contacts for the following alarms:

mains failure

general alarm

battery low

bypass active

For more information please refer to the user manual that comes with the interface card.

4.3

SNMP Interface Card (option)

This card allows the data interface to be connected directly to an Ethernet network.
For more information please refer to the user manual that comes with the interface card.

fig. 7

RS232

DC

UPS

DATA TO UPS

DATA FROM

MAX: +48V 100mA

BYPASS ACTIVE

BATTERY LOW

GENERAL ALARM

MAINS FAILURE

REMOTE UPS

SHUT DOWN

RS232

PORT

5 = COMMON
8 = UPS CONNECTED

RS232

DC

RS232

2

6

5

1

7

3

8

4

9

DC

PnP

4  -  Communication

Summary of Contents for NetPro Series

Page 1: ...nufactured by GE Digital Energy General Electric Company Telephone 41 0 91 850 51 51 CH 6595 Riazzino Locarno Fax 41 0 91 850 51 44 Switzerland Website www gedigitalenergy com GE Digital Energy Techno...

Page 2: ...2 Normal operation indications 3 3 3 Auto off no load shutdown 3 3 4 Automatic bypass switch 3 3 5 Switching off 3 4 Use Screen Menus 3 4 1 Default menu 3 4 2 Status messages and alarm messages 3 4 2...

Page 3: ...D ROM and this manual Inspect the UPS for damage after unpacking If any damage is present please immediately notify the carrier and place of purchase IMPORTANT Before making any connection and switchi...

Page 4: ...y pack 9 fig 1 4 to the DC socket of the UPS 7 fig 1 4 You will hear a click when the cable is properly installed Block the DC connector install the small locking plate 9a fig 4 that came with the bat...

Page 5: ...orking wall outlet the battery charger is active the batteries are being charged 2 Switch on the UPS with the on off switch 12 fig 1 at the rear of the unit the green LED operation will illuminate 3 T...

Page 6: ...S will switch off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will automatically turn on again when...

Page 7: ...e RMS input voltage 12 time until sleep in minutes if activated 23min the calculated available runtime at present load The calculation is based on two figures the capacity of the battery set and the e...

Page 8: ...only after the default screen is displayed again In case of weak mains the yellow LED 16 on the front panel illuminates and the buzzer remains silent high priority alarms indicate situations in which...

Page 9: ...ee section 6 2 Perhaps the replace battery alarm occurs after a manual test which you started immediately after installation or after a power failure In this case the alarm may be incorrect as the bat...

Page 10: ...is inhibited due to voltage or frequency errors of the mains supply or if the bypass function has been disabled see 3 4 3 the UPS may automatically switch off within a few seconds load dependent Outp...

Page 11: ...and stored with OK 19 If a setting is stored and will disappear One of the default screens will appear after 20 seconds of no key activity Blocking settings Pressing OK 19 and 18 simultaneously in a...

Page 12: ...tched off when the remaining runtime is one step from zero Example suppose the runtime is counted down with 10 minute steps and the off autonomy time is set as mentioned above Despite of the 5 minute...

Page 13: ...s supplied by a generator set and the generator s frequency is often out of the UPS s input tolerances frequently occurring bypass error alarms see 3 4 2 2 will be the result During these alarms bypas...

Page 14: ...untdown occurs with steps of 20 minutes each and during the last 20 minutes before the batteries are empty the runtime will be displayed as 20 min 3 6 Other Features 3 6 1 Shutdown Using communication...

Page 15: ...refer to the manual of your interface package or via the front panel with the push buttons OK and The procedure is as follows From a default screen press push button 20 until the display shows If no...

Page 16: ...n In order to keep track of the capacity deterioration due to aging of the batteries we advise to perform a battery calibration test at least once per year During a battery calibration test the batter...

Page 17: ...eed due to other circumstances than already indicated by pin 6 7 9 Output converter overload Overtemperature pre alarm Battery failure Fan failure High charger voltage Bypass out of limits Inverter sh...

Page 18: ...PowerFLAG SerVICe Box for Modem Connection If you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem a programmed number can be dialed in case of a UPS alarm It a...

Page 19: ...mperature See 3 4 2 3 Allow the UPS to cool down Line cord not connected Read 2 2 Connect line cord Batteries not connected Contact your dealer or consult www gedigitalenergy com Dead wall socket outl...

Page 20: ...1 msec Overload capability The UPS is fully protected against overload Overload behaviour on line operation bypass enabled 110 during 5 minutes 150 during 2 seconds on line operation bypass disabled...

Reviews: