Whenever a malfunction occurs, first check external factors (e.g connections, temperature, humidity or
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently
check the thermal circuit breaker: it may be tripped. If so: reset it (see 1, fig.1) and be sure that the UPS is
not overloaded.
The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed,
or if the information is insufficient to solve the problem, please contact your dealer or consult
www.gedigitalenergy.com.

PROBLEM

POSSIBLE CAUSE

SOLUTION

UPS overload

Reduce load, reset TCB
(1, fig. 1)

Thermal Circuit Breaker (TCB)
tripped

System failure

Contact your dealer or consult
www.gedigitalenergy.com

Most probably an overload

See 3.4.2.3, reduce the load

LCD message 'on bypass'

Overtemperature

See 3.4.2.3
Allow the UPS to cool down

Line cord not connected

Read 2.2
Connect line cord

Batteries not connected

Contact your dealer or consult
www.gedigitalenergy.com

Dead wall socket outlet, or
mains voltage out of limits

Contact qualified electrician

UPS overtemperature

See 3.4.2.3
Allow UPS to cool down

Runtime too low to start up

See 3.2.3, wait or press OK

UPS will not switch on (without
using 'battery start')
and the output has been off for
a few secs.

Tripped Thermal Circuit Breaker

See above

UPS switched off automatically

UPS overtemperature

See 3.4.2.3
Allow UPS to cool down

Mains failure, battery
discharged

Wait until mains returns

Programmed shutdown in
progress

See 3.6.2

UPS received shut down
command from computer during
mains failure

See 3.6.1

The load is < 5% of the max.
load and no mains power is
present.
(No-load shutdown function is
active, see 3.3.3)

Wait until mains returns

LCD message ‘replace battery’

Battery test just after installation
or mains failure

Allow the UPS to recharge the
batteries

Battery test shows weak battery

Read 6.2, replace batteries

7  -  Troubleshooting

Summary of Contents for NetPro Series

Page 1: ...nufactured by GE Digital Energy General Electric Company Telephone 41 0 91 850 51 51 CH 6595 Riazzino Locarno Fax 41 0 91 850 51 44 Switzerland Website www gedigitalenergy com GE Digital Energy Techno...

Page 2: ...2 Normal operation indications 3 3 3 Auto off no load shutdown 3 3 4 Automatic bypass switch 3 3 5 Switching off 3 4 Use Screen Menus 3 4 1 Default menu 3 4 2 Status messages and alarm messages 3 4 2...

Page 3: ...D ROM and this manual Inspect the UPS for damage after unpacking If any damage is present please immediately notify the carrier and place of purchase IMPORTANT Before making any connection and switchi...

Page 4: ...y pack 9 fig 1 4 to the DC socket of the UPS 7 fig 1 4 You will hear a click when the cable is properly installed Block the DC connector install the small locking plate 9a fig 4 that came with the bat...

Page 5: ...orking wall outlet the battery charger is active the batteries are being charged 2 Switch on the UPS with the on off switch 12 fig 1 at the rear of the unit the green LED operation will illuminate 3 T...

Page 6: ...S will switch off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will automatically turn on again when...

Page 7: ...e RMS input voltage 12 time until sleep in minutes if activated 23min the calculated available runtime at present load The calculation is based on two figures the capacity of the battery set and the e...

Page 8: ...only after the default screen is displayed again In case of weak mains the yellow LED 16 on the front panel illuminates and the buzzer remains silent high priority alarms indicate situations in which...

Page 9: ...ee section 6 2 Perhaps the replace battery alarm occurs after a manual test which you started immediately after installation or after a power failure In this case the alarm may be incorrect as the bat...

Page 10: ...is inhibited due to voltage or frequency errors of the mains supply or if the bypass function has been disabled see 3 4 3 the UPS may automatically switch off within a few seconds load dependent Outp...

Page 11: ...and stored with OK 19 If a setting is stored and will disappear One of the default screens will appear after 20 seconds of no key activity Blocking settings Pressing OK 19 and 18 simultaneously in a...

Page 12: ...tched off when the remaining runtime is one step from zero Example suppose the runtime is counted down with 10 minute steps and the off autonomy time is set as mentioned above Despite of the 5 minute...

Page 13: ...s supplied by a generator set and the generator s frequency is often out of the UPS s input tolerances frequently occurring bypass error alarms see 3 4 2 2 will be the result During these alarms bypas...

Page 14: ...untdown occurs with steps of 20 minutes each and during the last 20 minutes before the batteries are empty the runtime will be displayed as 20 min 3 6 Other Features 3 6 1 Shutdown Using communication...

Page 15: ...refer to the manual of your interface package or via the front panel with the push buttons OK and The procedure is as follows From a default screen press push button 20 until the display shows If no...

Page 16: ...n In order to keep track of the capacity deterioration due to aging of the batteries we advise to perform a battery calibration test at least once per year During a battery calibration test the batter...

Page 17: ...eed due to other circumstances than already indicated by pin 6 7 9 Output converter overload Overtemperature pre alarm Battery failure Fan failure High charger voltage Bypass out of limits Inverter sh...

Page 18: ...PowerFLAG SerVICe Box for Modem Connection If you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem a programmed number can be dialed in case of a UPS alarm It a...

Page 19: ...mperature See 3 4 2 3 Allow the UPS to cool down Line cord not connected Read 2 2 Connect line cord Batteries not connected Contact your dealer or consult www gedigitalenergy com Dead wall socket outl...

Page 20: ...1 msec Overload capability The UPS is fully protected against overload Overload behaviour on line operation bypass enabled 110 during 5 minutes 150 during 2 seconds on line operation bypass disabled...

Reviews: