background image

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

 

NetworX

 Series  

NX-4V2 Control Panel 

Installation and Startup

WWW.DIYALARMFORUM.COM

Summary of Contents for NX-4V2

Page 1: ...NetworX Series NX 4V2 Control Panel Installation and Startup WWW DIYALARMFORUM COM ...

Page 2: ...out the written approval of GE Security Please refer to the current GE Security product catalog for detailed warranty information Main 800 727 2339 Technical Support 888 437 3287 Outside the US 903 845 6941 Sales Literature 800 547 2556 Main Fax 903 845 6811 Web www gesecurity com SAFETY SYMBOLS Warning Indicates a procedure practice condition or statement that if not strictly observed could resul...

Page 3: ...CAL DATA 9 FEATURE SELECTION DATA 9 PROGRAMMING EXAMPLES 10 IX LOADING FACTORY DEFAULTS 11 X ENROLLING MODULES AND KEYPADS 11 XI L QUICK START INSTALLATION 11 XII PROGRAMMING LOCATIONS 11 REPORTING EVENTS TO PHONE NUMBER 1 12 REPORTING EVENTS TO PHONE NUMBER 2 13 REPORTING EVENTS TO PHONE NUMBER 3 14 XIII DEFAULT ZONE TYPES CONFIGURATIONS 16 XIV PROGRAMMING WORKSHEETS 28 XV GLOSSARY 35 XVI APPENDI...

Page 4: ... 48 Zone LCD Keypad NX 1208E 8 Zone LED Keypad NX 200 Zone Doubling Kit Includes 100 3 74k and 100 6 98k resistors NX 1248E 48 Zone LCD Keypad NX 320E Smart Power Supply and Buss Extender NX 1308E 8 Zone LED Door Design Keypad NX 408E 8 Zone Wireless Expansion Module UL listed part 60 904 NX 1316E 16 Zone LED Door Design Keypad NX 416E 16 Zone Wireless Expansion Module UL listed part 60 904 NX 132...

Page 5: ...NX 4V2 Control 5 IV WIRING DIAGRAM WWW DIYALARMFORUM COM ...

Page 6: ...mum For those jurisdictions which allow the Priority zone to be used with smoke detectors AUX2 Connect negative lead of low current device relay LED install 1KΩ resistor in series with LED etc Connect positive lead of device to COM Current is limited to 250mA when output is negative and 250FA when output is positive DATA Connect to the data terminal on the keypads and the expanders Maximum number ...

Page 7: ...re is a system trouble pressing r 2 will still show the service menu 8 RESERVED This LED should always be off r 9 4 Set Keypad Number Enter r 9 4 program code The Service LED and the Instant LED will flash Enter the keypad number 1 8 Press r The Instant LED will illuminate steady and the Service LED will remain flashing Enter 1 The keypad will automatically exit this mode at this time r 9 5 Set el...

Page 8: ...icating it is waiting for a programming location to be entered Any location can be accessed by directly entering the desired programming location followed by If the location entered is a valid location the Armed LED will extinguish the Ready LED will illuminate and the binary data for the first segment of this location will be shown by the zone LED s While entering new data the Ready LED will begi...

Page 9: ...n attempt is made to program a number too large for a particular segment the keypad sounder will emit a triple beep indicating an error and remain in that segment awaiting a valid entry On the LCD keypad the number in the location will be displayed For locations with a maximum of 15 the hexadecimal equivalent will be displayed in parenthesis Example 11 B or 14 E FEATURE SELECTION DATA Feature sele...

Page 10: ...ata in the current segment FIGURE 2 Feature Selection Data Location 23 Segment 1 1 Quick Arm 2 Re Exit 3 Auto Bypass 4 Silent Keypad Panic 5 Audible Keypad Panic 6 Keypad Auxiliary 1 7 Keypad Auxiliary 2 8 Multi Keypad Tamper Press the key on the numeric keypad that corresponds to the feature you wish to enable disable When an LED is on a feature is enabled when off the feature is disabled For exa...

Page 11: ... connection to the central station L 1 ACCOUNT CODE FOR PHONE 1 6 numerical The account code sent when Phone 1 is dialed is programmed in location 1 Program a A10 in the segment immediately after the last digit of the account code If the account code is 6 digits long program all 6 segments L 2 COMMUNICATOR FORMAT FOR PHONE 1 1 numerical Location 2 contains the communicator format used to transmit ...

Page 12: ...tore and Low Battery Restore 6 Bell Cut Telephone Line Cut Bell Cut Restore Telephone Line Restore 7 Test Reports 8 Start and End programming Download complete Segment 2 1 Zone and Box Tamper and Tamper Restore 2 Auxiliary Power Overcurrent and Restore 3 Wireless Sensor Missing and Restore 4 Wireless Sensor Low Battery and Restore 5 Expander Trouble and Restore 6 Fail To Communicate 7 Zone Activit...

Page 13: ...nt 2 1 Zone and Box Tamper and Tamper Restore 2 Auxiliary Power Overcurrent and Restore 3 Sensor Missing and Restore 4 Sensor Low Battery and Restore 5 Expander Trouble and Restore 6 Fail To Communicate 7 Zone Activity Monitor 8 Reserved 11 RESERVED 12 PROGRAMMING PHONE 3 20 numerical Phone 3 is programmed in location 12 A 14 indicates the end of the phone number Delays of four seconds can be prog...

Page 14: ...losings 3 Zone Bypass and Bypass Restores 4 Zone Trouble and Trouble Restores 5 Power Fail Low Battery Power Restore and Low Battery Restore 6 Bell Cut Telephone Line Cut Bell Cut Restore Telephone Line Restore 7 Test Reports 8 Start and End programming Download complete Segment 2 1 Zone and Box Tamper and Tamper Restore 2 Auxiliary Power Overcurrent and Restore 3 Sensor Missing and Restore 4 Sens...

Page 15: ...atures that can be accessed or are visible to the user from the keypad of the system In addition certain communicator reports are enabled in location 23 For specific definitions refer to the Glossary beginning on page 35 Segment 1 1 On enables the Quick Arm feature 2 On enables the Re exit feature 3 On enables the Automatic Bypass feature 4 On enables the Silent Keypad Panic feature overrides the ...

Page 16: ...ting a trouble if the zone is open 9 ENTRY EXIT DELAY 2 A trip will start entry delay 2 The lack of a trip during exit delay will enable the Automatic Bypass or Instant mode if so programmed 10 24 HOUR SILENT SUPERVISED Creates an instant silent alarm regardless of the armed state of the control panel It will display on the keypad 11 RESERVED 12 INTERIOR FOLLOWER WITH CROSS ZONE ENABLED This zone ...

Page 17: ... is armed and no entry or exit delay is being timed It is delayed during entry and exit delay times It will send a report if the zone activity time is reached without a change of state Refer to Location 40 Segment 11 This zone will automatically bypass if enabled in Segment 1 of Location 23 30 ENTRY EXIT WITH ACTIVITY SUPERVISION ENABLED A trip will start entry delay 1 It will send a report if the...

Page 18: ...erved 7 Use internal crystal for clock 8 Disable Temporal Siren on Fire NOTE Do NOT disable for UL listed systems Segment 6 1 Reserved 2 Reserved 3 Enable for Zone Activity in Hours not Days 4 Enable Daylight Savings Time DST 5 Reserved 6 On to disable Clean Me report At default bit is OFF enabled 7 Disable Start End Test report At default bit is OFF enabled 8 Reserved Segment 7 Reserved L 38 SWIN...

Page 19: ... enabled all arm disarm codes and the Go To Program Code are 6 digits If this option is enabled the default user 1 code is 1 2 3 4 5 6 NOTE IF YOU ENABLE THIS OPTION VERIFY THAT THE GO TO PROGRAM CODE IS A SIX DIGIT CODE BEFORE EXITING PROGRAMMING 2 On requires code entry for r 9 8 perform call back download and r 9 9 answer incoming call for download functions 3 Enable Auto Cancel Abort Refer to ...

Page 20: ... Over current 3 Trouble Alarm 22 Disarmed State 41 Box Tamper 4 Tamper Alarm 23 Ready 42 Siren Tamper 5 Yelping Siren Burglary 24 Not Ready 43 Any Open 6 Temporal Siren Fire 25 Fire 44 Any Short 7 Any Siren 26 Fire Trouble 45 Any Fault Open Short on Non Fire Zone 8 Any Bypass 27 Chime 46 Any Alarm 9 AC Fail 28 Expander Trouble 47 Beeping Keypad 10 Low Battery 29 Dynamic Battery Test Time 48 Code E...

Page 21: ... Location 54 selects which days of the week the system is open On these days Aarm only after close window codes will be able to arm and disarm during open window NOTE If system is not programmed to be opened and is programmed to Auto Arm Location 55 the NX 4V2 will try to arm every 45 minutes for the duration of the closed period unless Auto Retry is disabled in location 55 On days not selected he...

Page 22: ... 2 numerical Location 65 contains the digits that will be sent for a 4 2 format if the keypad Panic is enabled in location 23 Box on pg 22 66 KEYPAD MULTIPLE CODE ENTRY TAMPER COMM CODE 2 numerical Location 66 contains the digits that will be sent for a 4 2 format if the keypad Multiple Code Entry Tamper is enabled in location 23 Box on pg 22 67 BOX TAMPER RESTORE COMMUNICATOR CODE 4 numerical Loc...

Page 23: ...cal Location 82 contains the digits for a 4 2 format that will be sent if End Downloading Reporting is enabled Segments 1 and 2 are Reserved Segment 3 contains the digit of the End Download Reporting Segment 4 contains the digit of the End Download Reporting Box on pg 22 Note A start download report will be sent to the internal event log 83 CANCEL COMMUNICATOR CODE 1 numerical Location 83 contains...

Page 24: ...o Location 110 on page 23 for details 115 ZONE TYPE 3 CHARACTERISTIC SELECT 5 feature select Use Zone Type Characteristic Selections described in Location 111 page 23 116 ZONE TYPE 4 ALARM EVENT CODE 1 numerical Location 116 contains the event code sent for a Contact ID or SIA report The desired event code should be chosen from the list on page 39 The zone ID will be that zone that is in alarm If ...

Page 25: ...ELECT 5 feature select Use Zone Type Characteristic Selections described in Location 111 page 23 134 ZONE TYPE 13 ALARM EVENT CODE 1 numerical Location 134 contains the event code sent for a Contact ID or SIA report The desired event code should be chosen from the list on page 39 The zone ID will be that zone that is in alarm If 4 2 format is being used refer to Location 110 on page 23 for details...

Page 26: ...cation 110 on page 23 for details 153 ZONE TYPE 22 CHARACTERISTIC SELECT 5 feature select Use Zone Type Characteristic Selections described in Location 111 page 23 154 ZONE TYPE 23 ALARM EVENT CODE 1 numerical Location 154 contains the event code sent for a Contact ID or SIA report The desired event code should be chosen from the list on page 39 The zone ID will be that zone that is in alarm If 4 ...

Page 27: ...to Location 110 on page 23 for details 167 ZONE TYPE 29 CHARACTERISTIC SELECT 5 feature select Use Zone Type Characteristic Selections described in Location 111 page 23 168 ZONE TYPE 30 ALARM EVENT CODE 1 numerical Location 168 contains the event code sent for a Contact ID or SIA report The desired event code should be chosen from the list on page 39 The zone ID will be that zone that is in alarm ...

Page 28: ...res 2 Open Close 3 Bypass 4 Zone Trouble 5 Power Trouble AC Failure or Low Battery 6 Siren Telephone Fault 7 Test Reports 8 Program Download Log Full 1 Tampers 2 Short Circuit 3 Sensor Lost 4 Sensor Low Battery 5 Expander Trouble 6 Failure To Communicate 7 Zone Activity Monitor 8 Reserved 11 13 RESERVED 12 13 PHONE 3 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 __ __ __ __ __ __ __ ...

Page 29: ...se 2 Bypass 3 Restore 4 Trouble 5 Tamper 6 Cancel 7 Recent Closing 8 Exit Error Segment 4 Circle Numbers To Program 1 Late to Close Early to Open 2 Auto Arm in Stay Mode 3 Disables door delays in Night mode 4 8 Reserved Segment 5 RESERVED L 24 16 ENTRY EXIT TIMERS Segment 1 Entry Time 1 30 Segment 2 Exit Time 1 60 Segment 3 Entry Time 2 30 Segment 4 Exit Time 2 60 Segments 5 6 Reserved L 25 17 ZON...

Page 30: ...Reserved Segment 7 RESERVED L 38 18 SWINGER SHUTDOWN COUNT 1 _ L 39 18 KEYPAD SOUNDER CONTROL Segment 1 Circle numbers to program 1 Keypad sounds for Telephone Line Cut when in the Armed state 2 Keypad sounds for Telephone Line Cut when in the Disarmed state 3 Keypad sounds upon AC Power Failure 4 Keypad sounds upon Low Battery Detection 5 Keypad sounds during Cross Zone Trip Time 6 Keypad sounds ...

Page 31: ...served 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 47 20 AUXILIARY OUTPUT 1 EVENT TIME Segment 1 Event number for output 1 0 Burglary alarm Segment 2 Timing for output 1 10 seconds 48 20 AUXILIARY OUTPUT 2 EVENT TIME Segment 1 Event number for output 2 1 Fire alarm Segment 2 Timing for output 2 10 seconds 49 50 RESERVED L 51 20 AUTOTEST CONTROL Seg 1 Program a 1 if the interval is hours a 0 if in days Add a A...

Page 32: ...PHONE LINE CUT LINE CUT RESTORE 0 0 0 0 _ _ _ _ 73 22 Reserved 0 0 0 0 _ _ _ _ 74 23 EXPANDER TROUBLE EXP TROUBLE RESTORE 0 0 0 0 _ _ _ _ 75 23 FAILURE TO COMMUNICATE 0 0 _ _ 76 23 LOG FULL COMMUNICATOR CODE 0 0 _ _ 77 23 OPENING CODE COMMUNICATOR CODE 0 _ 78 23 CLOSING COMMUNICATOR CODE 0 _ 79 23 AUTOTEST COMMUNICATOR CODE 0 0 _ _ 80 23 RECENT CLOSING AND EXIT ERROR 0 0 _ _ 81 23 START PROGRAMMIN...

Page 33: ...7 125 45678 0 0 __ __ __ __ __ 134 ZONE TYPE 13 ALARM EVENT CODE 4 __ 135 ZONE TYPE 13 CHARACTERISTIC SELECT 0 12458 5678 0 0 __ __ __ __ __ 136 ZONE TYPE 14 ALARM EVENT CODE 7 __ 137 ZONE TYPE 14 CHARACTERISTIC SELECT 5 12456 5678 0 0 __ __ __ __ __ 138 ZONE TYPE 15 ALARM EVENT CODE 5 __ 139 ZONE TYPE 15 CHARACTERISTIC SELECT 457 1256 5678 0 0 __ __ __ __ __ 140 ZONE TYPE 16 ALARM EVENT CODE 4 __...

Page 34: ...E 30 CHARACTERISTIC SELECT 5 1245 5678 1 0 __ __ __ __ __ 170 205 RESERVED 206 DAYS OF THE WEEK AUTO DISARMING WILL OCCUR Sunday Monday Tuesday Wednesday Thursday Friday Saturday Reserved Segment 1 1 2 3 4 5 6 7 8 ZONE WORKSHEET 1 5 2 6 3 7 4 8 NOTES WWW DIYALARMFORUM COM ...

Page 35: ...es ADialer Delay must be enabled in the ACharacteristic Select of locations 110 169 Zone Types Loc 41 pg 19 Auto Test This feature will cause the panel to call the central station to report a communicator test at a specified interval Loc 51 pg 20 Auxiliary Outputs The NX 4V2 has 2 programmable outputs that can be used to activate relays LED s etc See the terminal description on pg 6 and Loc 45 50 ...

Page 36: ...can be found on page 41 Loc 37 pg 17 Fail to Communicate The NX 4V2 will illuminate the Service LED if a report fails to reach the central station If enabled when the next report is successfully communicated a Fail to Communicate code will be reported Loc 37 pg 17 Fire Alarm Verification When enabled the NX 4V2 will verify a Fire alarm by requiring more than one trip on a smoke detector within a s...

Page 37: ...en the central station receiver acknowledges the closing report It can also give one blast for remote keyswitch arming and two blasts for remote disarming Loc 37 pg 17 Siren Supervision The NX 4V2 has a ASiren Supervision circuit that will constantly monitor the siren on the NX 4V2 and can be programmed to report if the wires are cut Loc 37 pg 17 Silent Exit Option The exit delay can be silenced b...

Page 38: ...t reported to the receiver The Service LED will illuminate when either condition exists Loc 37 pg 17 Zone Activity Monitor This feature will send a report to the central station when a particular zone does not change conditions within the specified number of days programmed Loc 40 110 169 pg 19 23 27 Zone Bypassed Sounder Alert If this feature is enabled the NX 4V2 will beep the keypad sounder upo...

Page 39: ...PAD AUXILIARY 2 100 MA KEYPAD PANIC audible 120 PA KEYPAD PANIC silent 121 HA KEYPAD TAMPER 137 TA LOW BATTERY device number 309 YT LOW BATTERY RESTORE device number 309 YR MANUAL TEST 601 RX OPEN user number 401 OP RECENT CLOSE user number 401 CR RF SENSOR LOST zone number 381 T RF SENSOR RESTORE zone number 381 R SENSOR BATTERY RESTORE zone number 384 XR SENSOR LOW BATTERY zone number 384 XT SIR...

Page 40: ...A Water Alarm 18 QA Emergency Alarm 19 SA Sprinkler Alarm 20 ZA Freeze Alarm 21 KH High Temp Alarm 22 FA Manual Fire Alarm The NX 4V2 has the ability to report Ademco Contact ID transmissions Each report in Contact ID consists of an Event Code and a Zone ID The zone ID is the zone that created the alarm The event code will come from the chart below and be programmed in the zone type event code Pro...

Page 41: ... 1 on 36 Switch 3 on 25 Switch 2 on 37 Switch 1 3 on 26 Switches 1 2 on 38 Switch 2 3 on 27 Switch 3 on 39 Switch 1 2 3 on 28 Switches 1 3 on 32 All switches off 29 Switches 2 3 on 33 Switch 1 on 30 Switch 1 2 3 on 34 Switch 2 on 31 XIX APPENDIX 4 USER ID OR ZONE ID HEX DIGIT FOR 4 2 FORMATS The following appendix applies only to slow formats locations 56 83 lower digit The digit programmed in the...

Page 42: ...ent from the telephone line to determine if it is the customers equipment that is not functioning properly If the problem is with the device the customer shall discontinue use until it is repaired EQUIPMENT INFORMATION Manufacturer Of Connecting Equipment CADDX CONTROLS INC FCC Registration Number US GCQAL01BNX V2 RINGER EQUIVALENCE 0 1 B XXI INDUSTRY CANADA INFORMATION NOTICE The Industry Canada ...

Page 43: ...in the countries marked with a check and may have interworking problems with the countries that are not checked Due to the inherent differences in the individual PSTNs certain software settings may need to be adjusted on a country to country basis If it is desired to use this equipment on a network other than the one on which it was originally installed you should contact your equipment supplier A...

Page 44: ...rglary applications the maximum entry and exit delay times shall be 45 and 60 seconds respectively The exit delay time shall not exceed 60 seconds for commercial burglar alarm applications The keyswitch option shall not be used The telephone line monitor shall be enabled The Telephone Line Cut delay shall not exceed 90 seconds 24 hour communicator test transmission is required For 24 hours of stan...

Page 45: ... mA 34 AH 1 Amp 200 mA 17 AH 1 Amp Calculations based on three 17 Amp batteries K IMPORTANT If separate power supplies are necessary to accommodate additional devices safety standards require that each power supply be prominently marked with adequate instructions for removing all power from the unit Dispose of used batteries according to the manufacturer s instructions and or local government auth...

Page 46: ...0 240 sec Entry 2 Delay 24 3 30 30 240 sec Abort Window for Non Fire Zones Dialer Delay 40 8 30 Enabled may be disabled by zone zone type Abort Window Time for Non Fire Zones Dialer Delay 40 8 30 15 45 sec NOTE Combined Abort window and Entry Delay must not exceed 1 minute Abort Annunciation This feature is non programmable in the panel Flashing Cancel LED goes off when disarming Enabled Cancel An...

Page 47: ...NOTES WWW DIYALARMFORUM COM ...

Page 48: ...ees F LED KEYPAD Current Draw 130 mA max Zones Normal w o Sounder 55 mA Dimensions 6 4 Wide 4 0 High 1 1 Deep NX148E LCD KEYPAD Current Draw 110 mA max w o Sounder 75 mA Dimensions 6 4 Wide 5 3 High 1 0 Deep METAL ENCLOSURE DIMENSION 9 25 Wide 8 25 High 3 50 Deep SHIPPING WEIGHT 9 lbs Main 800 727 2339 Technical Support 888 437 3287 Outside the US 903 845 6941 Sales Literature 800 547 2556 Main Fa...

Reviews: