P54A/B/C/E
Appendix B - Settings and Signals
P54xMED-TM-EN-1
B127
MENU TEXT
COL
ROW
DEFAULT SETTING
AVAILABLE OPTIONS
DESCRIPTION
characters.
The community name setting must be the same in both the SNMP Manager and the IED.
COMMISSION TESTS
0F
00
This column contains commissioning test settings
Opto I/P Status
0F
01
Opto I/P Status
[Binary Flag (32) Indexed String]
This menu cell displays the status of the available IED’s opto-isolated inputs as a binary string, a ‘1’ indicating an energized opto-isolated
input and a ‘0’ a de-energized one.
Relay O/P Status
0F
02
Relay O/P Status
[Binary Flag (32) Indexed String]
This menu cell displays the status of the digital data bus (DDB) signals that result in energization of the available output relays as a binary
string, a ‘1’ indicating an operated state and ‘0’ a non-operated state.
When the ‘Test Mode’ cell is set to ‘Enabled’ the ‘Relay O/P Status’ cell does not show the current status of the output relays and hence can
not be used to confirm operation of the output relays. Therefore it will be necessary to monitor the state of each contact in turn.
Test Port Status
0F
03
Test Port Status
[Binary Flag (8) Indexed String]
This menu cell displays the status of the eight digital data bus (DDB) signals that have been allocated in the ‘Monitor Bit’ cells.
Monitor Bit 1
0F
05
1060
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or
via the monitor/download port.
Monitor Bit 2
0F
06
1062
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or
via the monitor/download port.
Monitor Bit 3
0F
07
1064
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or
via the monitor/download port.
Monitor Bit 4
0F
08
1066
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or
via the monitor/download port.
Monitor Bit 5
0F
09
1068
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or
via the monitor/download port.
Monitor Bit 6
0F
0A
1070
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or
via the monitor/download port.
Monitor Bit 7
0F
0B
1072
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or
via the monitor/download port.
Monitor Bit 8
0F
0C
1074
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
The eight ‘Monitor Bit’ cells allow the user to select the status of which digital data bus signals can be observed in the ‘Test Port Status’ cell or
via the monitor/download port.
IED Test Mode
0F
0D
Disabled
Disabled
Test Mode
Contacts Blocked
[Indexed String]
The IED Test Mode menu cell is used to allow online testing to be performed on the IED without operation of the trip contacts. It also enables
a facility to directly test the output contacts by applying menu controlled test signals.
This setting influences the processing of control service frames with an IEC61850 Test mode flag. It does not influence the processing of
other incoming data, such as GOOSE.
To select test mode the IED Test Mode menu cell should be set to ‘Test’, which takes the IED out of service. It also causes an alarm condition
Summary of Contents for P4A
Page 2: ......
Page 20: ...Contents P54A B C E xviii P54xMED TM EN 1 ...
Page 27: ...CHAPTER 1 INTRODUCTION ...
Page 28: ...Chapter 1 Introduction P54A B C E 2 P54xMED TM EN 1 ...
Page 38: ...Chapter 1 Introduction P54A B C E 12 P54xMED TM EN 1 ...
Page 39: ...CHAPTER 2 SAFETY INFORMATION ...
Page 40: ...Chapter 2 Safety Information P54A B C E 14 P54xMED TM EN 1 ...
Page 52: ...Chapter 2 Safety Information P54A B C E 26 P54xMED TM EN 1 ...
Page 53: ...CHAPTER 3 HARDWARE DESIGN ...
Page 54: ...Chapter 3 Hardware Design P54A B C E 28 P54xMED TM EN 1 ...
Page 86: ...Chapter 3 Hardware Design P54A B C E 60 P54xMED TM EN 1 ...
Page 87: ...CHAPTER 4 SOFTWARE DESIGN ...
Page 88: ...Chapter 4 Software Design P54A B C E 62 P54xMED TM EN 1 ...
Page 99: ...CHAPTER 5 CONFIGURATION ...
Page 100: ...Chapter 5 Configuration P54A B C E 74 P54xMED TM EN 1 ...
Page 120: ...Chapter 5 Configuration P54A B C E 94 P54xMED TM EN 1 ...
Page 121: ...CHAPTER 6 CURRENT DIFFERENTIAL PROTECTION ...
Page 122: ...Chapter 6 Current Differential Protection P54A B C E 96 P54xMED TM EN 1 ...
Page 149: ...CHAPTER 7 AUTORECLOSE ...
Page 150: ...Chapter 7 Autoreclose P54A B C E 124 P54xMED TM EN 1 ...
Page 207: ...CHAPTER 8 CB FAIL PROTECTION ...
Page 208: ...Chapter 8 CB Fail Protection P54A B C E 182 P54xMED TM EN 1 ...
Page 219: ...CHAPTER 9 CURRENT PROTECTION FUNCTIONS ...
Page 220: ...Chapter 9 Current Protection Functions P54A B C E 194 P54xMED TM EN 1 ...
Page 244: ...Chapter 9 Current Protection Functions P54A B C E 218 P54xMED TM EN 1 ...
Page 247: ...CHAPTER 10 VOLTAGE PROTECTION FUNCTIONS ...
Page 248: ...Chapter 10 Voltage Protection Functions P54A B C E 222 P54xMED TM EN 1 ...
Page 261: ...CHAPTER 11 FREQUENCY PROTECTION FUNCTIONS ...
Page 262: ...Chapter 11 Frequency Protection Functions P54A B C E 236 P54xMED TM EN 1 ...
Page 268: ...Chapter 11 Frequency Protection Functions P54A B C E 242 P54xMED TM EN 1 ...
Page 269: ...CHAPTER 12 MONITORING AND CONTROL ...
Page 270: ...Chapter 12 Monitoring and Control P54A B C E 244 P54xMED TM EN 1 ...
Page 300: ...Chapter 12 Monitoring and Control P54A B C E 274 P54xMED TM EN 1 ...
Page 301: ...CHAPTER 13 SUPERVISION ...
Page 302: ...Chapter 13 Supervision P54A B C E 276 P54xMED TM EN 1 ...
Page 312: ...Chapter 13 Supervision P54A B C E 286 P54xMED TM EN 1 ...
Page 323: ...CHAPTER 14 DIGITAL I O AND PSL CONFIGURATION ...
Page 324: ...Chapter 14 Digital I O and PSL Configuration P54A B C E 298 P54xMED TM EN 1 ...
Page 336: ...Chapter 14 Digital I O and PSL Configuration P54A B C E 310 P54xMED TM EN 1 ...
Page 337: ...CHAPTER 15 FIBRE TELEPROTECTION ...
Page 338: ...Chapter 15 Fibre Teleprotection P54A B C E 312 P54xMED TM EN 1 ...
Page 354: ...Chapter 15 Fibre Teleprotection P54A B C E 328 P54xMED TM EN 1 ...
Page 355: ...CHAPTER 16 ELECTRICAL TELEPROTECTION ...
Page 356: ...Chapter 16 Electrical Teleprotection P54A B C E 330 P54xMED TM EN 1 ...
Page 366: ...Chapter 16 Electrical Teleprotection P54A B C E 340 P54xMED TM EN 1 ...
Page 367: ...CHAPTER 17 COMMUNICATIONS ...
Page 368: ...Chapter 17 Communications P54A B C E 342 P54xMED TM EN 1 ...
Page 439: ...CHAPTER 18 CYBER SECURITY ...
Page 440: ...Chapter 18 Cyber Security P54A B C E 414 P54xMED TM EN 1 ...
Page 457: ...CHAPTER 19 INSTALLATION ...
Page 458: ...Chapter 19 Installation P54A B C E 432 P54xMED TM EN 1 ...
Page 471: ...CHAPTER 20 COMMISSIONING INSTRUCTIONS ...
Page 472: ...Chapter 20 Commissioning Instructions P54A B C E 446 P54xMED TM EN 1 ...
Page 513: ...CHAPTER 21 MAINTENANCE AND TROUBLESHOOTING ...
Page 514: ...Chapter 21 Maintenance and Troubleshooting P54A B C E 488 P54xMED TM EN 1 ...
Page 530: ...Chapter 21 Maintenance and Troubleshooting P54A B C E 504 P54xMED TM EN 1 ...
Page 531: ...CHAPTER 22 TECHNICAL SPECIFICATIONS ...
Page 532: ...Chapter 22 Technical Specifications P54A B C E 506 P54xMED TM EN 1 ...
Page 558: ...Chapter 22 Technical Specifications P54A B C E 532 P54xMED TM EN 1 ...
Page 559: ...APPENDIX A ORDERING OPTIONS ...
Page 560: ...Appendix A Ordering Options P54A B C E P54xMED TM EN 1 ...
Page 565: ...APPENDIX B SETTINGS AND SIGNALS ...
Page 566: ...Appendix B Settings and Signals P54A B C E P54xMED TM EN 1 ...
Page 790: ...Appendix B Settings and Signals P54A B C E B224 P54xMED TM EN 1 ...
Page 835: ...APPENDIX C WIRING DIAGRAMS ...
Page 836: ...Appendix C Wiring Diagrams P54A B C E P54xMED TM EN 1 ...
Page 849: ......