Chapter 4. Ladder Diagram (LD) Programming
GFK-2950C
February 2018
93
4.4.2
Fault Contact
A Fault contact (FAULT) detects faults in discrete or analog reference addresses, or locates faults
(rack, slot, bus, module).
■
To guarantee correct indication of module status, use the reference address (%I, %Q, %AI, %AQ) with the
FAULT/NOFLT contacts.
■
To locate a fault, use the rack, slot, bus, module fault locating system variable with a FAULT/NOFLT
contact.
Note:
The fault indication of a given module is cleared when the associated fault is cleared from the
fault table.
■
For I/O point fault reporting, you must enable point fault references in Hardware Configuration.
FAULT passes power flow if its associated variable or location has a point fault.
Operands
Parameter Description
Allowed Operands
Optional
BWVAR
The variable associated with the
FAULT contact
variables in %I, %Q, %AI, and %AQ memories, and
predefined fault-locating references
No