Chapter 6. Service Request Function
GFK-2950C
February 2018
279
6.2.5
To read the current timer state and value without changing
either:
Enter SVC_REQ 1 with this parameter block:
Address
3
A 1
ignored
Output
SVC_REQ 1 returns the timer state and value in the same parameter block references:
Address
0 = Normal Sweep
1 = Constant Sweep
A 1
Current timer value
If the word a 1 contains the hexadecimal value FFFF, no timer value has been programmed.
SVC_REQ 1 Example
If contact OV_SWP is set, the Constant Sweep Timer is read, the timer is increased by 2 ms, and the
new timer value is sent back to the CPU. The parameter block is at location %R3050. The example
logic uses discrete internal coil %M0001 as a temporary location to hold the successful result of the
first rung line. On any sweep in which OV_SWP is not set, %M00001 is turned off.