Chapter 3. Program Data
50
PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual
GFK-2950C
Non-Configurable Faults
Non-Configurable Faults
(Action)
Description
#SBUS_FL (fatal)
System bus failure. The CPU was not able to access the VME bus.
BUSGRT-NMI error.
#HRD_CPU (fatal)
CPU hardware fault, such as failed memory device or failed serial port.
#HRD_SIO (diagnostic)
Non-fatal hardware fault on any module in the system.
#SFT_SIO (diagnostic)
Non-recoverable software error in a LAN interface module.
#PB_SUM (fatal)
Program or block checksum failure during power-up or in RUN Mode.
#LOW_BAT (diagnostic)
The low battery indication is not supported for all CPU modules. For
details, refer to
The CPU may set this contact when an I/O module or special-purpose
module has reported a low battery. In this case, a fault will be reported in
the I/O Fault Table.
To clear this bit, clear the CPU fault table or power cycle the CPU.
#OV_SWP (diagnostic)
Constant sweep time exceeded.
#SY_FULL, IO_FULL (diagnostic)
CPU fault table full
I/O Fault Table full
#IOM_FLT (diagnostic)
Point or channel on an I/O module
—
a partial failure of the module.
#APL_FLT (diagnostic)
Application fault.
#ADD_RCK (diagnostic)
New rack added, extra, or previously faulted rack has returned.
#ADD_IOC (diagnostic)
Extra I/O Bus Controller or reset of I/O Bus Controller.
#ADD_IOM (diagnostic)
Previously faulted I/O module is no longer faulted or extra I/O module.
#ADD_SIO (diagnostic)
New intelligent option module is added, extra, or reset.
#NO_PROG (information)
No application program is present at power-up. Should only occur the
first time the CPU is powered up or if the user memory is not retained.
#BAD_RAM (fatal)
Corrupted program memory at power-up. Program could not be read
and/or did not pass checksum tests.
#WIND_ER (information)
Window completion error. Servicing of Programmer or Logic Window was
skipped. Occurs in Constant Sweep mode.
#BAD_PWD (information)
Change of privilege level request to a protection level was denied; bad
password.
#NUL_CFG (fatal)
No configuration present upon transition to RUN Mode. Running without
a configuration is similar to suspending the I/O scans.
#SFT_CPU (fatal)
CPU software fault. A non-recoverable error has been detected in the
CPU. May be caused by Watchdog Timer expiring.
#MAX_IOC (fatal)
The maximum number of bus controllers has been exceeded. The CPU
supports 32 bus controllers.
#STOR_ER (fatal)
Download of data to CPU from the programmer failed; some data in CPU
may be corrupted.
Summary of Contents for PACSystems RSTi-EP
Page 357: ......