Chapter 3
.
PROFIBUS Network Adapters
GFK-2746B
PACSystems* RSTi PROFIBUS and PROFINET Network Adapter
–August 2013
45
3.2.7.2
Station Address and Quick Startup Mode Setup
Station Address Setup for STXPBS001
Each PROFIBUS Adapter must have a unique address (from 1 to 99) so that it can be
addressed independently from other nodes. The address 0 is reserved to identify a broadcast
exchange. No response is returned to broadcast requests sent by the master.
Figure 26: MAC ID of a slave node
The above figure shows MAC ID 27(=2*10 + 7*1) of a slave node.
Note that if the station number is once set and an attempt is made to change the station
number, it would result in communication errors. Power cycle the module and download the
new assigned station number to restore communication.
■
Communication Speed Setting
Refer to GEIP PROFIBUS master module settings to change the communication
speed.