Chapter 3
.
PROFIBUS Network Adapters
46
PACSystems* RSTi PROFIBUS and PROFINET Network Adapter
–August 2013
GFK-2746B
Station Address Setup for STXPBS
*
Each PROFIBUS Adapter must have a unique Node Station address (from 0 to 99) so that it
can be addressed independently from other nodes.
The figure below shows Dip Switch #1~7 setting.
Figure 27: DIP Switch
■
Node Station Address Setting Example
In order to change station ID to No. 20 (Bin 10100), Dip switch No.3 and 5 must be ON and
others must be OFF.
Figure 28: Node Station Address Setting
■
Mode Setting
Table 27: Mode Setting
Dip #8.
Start Mode
OFF
Normal Booting
ON
Quick Booting
Note:
Directions for setting Node Number (Station number)
1. Select address within the range of 00 to 99
(Station no. 00
2. Station number setting out of the range will cause communication error.
3. Duplicating Station No. will cause communication error