Chapter 3
.
PROFIBUS Network Adapters
GFK-2746B
PACSystems* RSTi PROFIBUS and PROFINET Network Adapter
–August 2013
65
3.3.10
Diagnostics
Byte
Item
Description
0
Station status 0
PROFIBUS Standard
Diagnostic
1
Station status 0
2
Station status 0
3
Master Address
4
PNO Ident Number High
5
PNO Ident Number Low
6
ID Diagnostic Header
Extended Diagnostic
(ID Related Diagnostic)
7
Diagnostic allocation (Slot0~7)
8
Diagnostic allocation (Slot8~15)
9
Diagnostic allocation (Slot16~23)
10
Diagnostic allocation (Slot24~31)
11
Diagnostic allocation (Slot32~39)
12
Reserved
13
14
15
Device Status Diagnostic Header
Extended Diagnostic
(Device Status)
16
Status Type (0xA0:Manufacture-specific)
17
Slot Number
18
Status differentiation (0:No differentiation)
19
Status message
20
Reserved
■
ID Related Diagnostic
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
6
ID Diagnostic Header (0x45)
7
Slot 7
Slot 6
Slot 5
Slot 4
Slot 3
Slot 2
Slot 1
STXPB
S001
8
Slot 15
Slot 14 Slot 13
Slot 12
Slot 11
Slot 10
Slot 9
Slot 8
9
Slot 23
Slot 22 Slot 21
Slot 20
Slot 19
Slot 18
Slot 17
Slot 16
10
Slot 31
Slot 30 Slot 29
Slot 28
Slot 27
Slot 26
Slot 25
Slot 24
11
Reserved
Slot 32
Summary of Contents for PACSystems RSTi
Page 4: ......
Page 8: ......
Page 88: ...88 PACSystems RSTi PROFIBUS and PROFINET Network Adapter August 2013 GFK 2746B...