5-14
RSTi Network Adapter Manual User Manual -January 2012
GFK-2746
5
STXPNS001 Parameter Settings
STXPNS001 Parameter
The following table describes the STXPNS001 parameter settings.
Table 44: STXPNS001: Parameter Setting and Description
Parameter
Setting
Description
Word data type
MOTOLORA *
Big Endian format(MSB-LSB)
INTEL
Little Endian format(LSB-MSB)
Stop action
Clear output image to 0 *
All outputs are set to 0.
Hold last valid output image
All Outputs hold the last valid
output values.
Depends on IO’s fault action
parameters
The communication between
STXPNS001 and modules will be
stopped and each module will
control its IO Data according to
the Fault Action selected for it.
Reaction on RSTi Bus error Clear input image
The input values are cleared
Hold last image
The input values hold the last
valid values.
Auto reset *
STXPNS001 performs reset.
Disconnect PROFINET
Stop the communication with
Controller.
* Default settings
Summary of Contents for PACSystems RSTi