Chapter 1
.
Introduction
1.3
Specifications
RX3i Genius Communications Gateway Specifications
PROFINET Support
PROFINET version 2.3 Class A IO-Device
CPU Compatibility
RX3i CPE330
RX3i CPE305/CPE310 with firmware version 8.15 or later
RX3i CPU315/CPU320/CRU320 with firmware version 8.15 or later
PNC001 Compatibility
Firmware version 2.05 or later
Embedded PROFINET Compatibility
RX3i CPE330 embedded PROFINET with firmware version 8.90 or
later
Proficy* Machine Edition Compatibility
Machine Edition 8.0 or later
Power Requirements
External 24Vdc: (±10%) 0.2A
Operating Temperature Range
0 to 60°C
Number of Port Connectors
Two RJ-45
Local Area Network (LAN)
IEEE 802.2 Logical Link Control Class I
IEEE 802.3 CSMA/CD Medium Access Control 10/100 Mbps
Status Data
64 (two banks of 32 bits)
Genius Bus Support
Supports One Genius Bus.
Serial 1, Serial 2, Shield In and Shield Out, as marked.
Up to 31 additional devices supported per Genius Bus.
Selectable Baud Rate, per Genius specifications.
Genius Hot Standby and Duplex Redundancy supported.
HHM Compatibility
IC66* HHM501
Other Genius Compatibility
See table in Section 1.9
SD Card
2GB or smaller. Not compatible with SDHC or SDXC cards.
Configuration
GSDML file is available on the Support website for download
and import into Proficy Machine Edition. The GSDML
supporting a firmware release is part of the firmware
upgrade kit available on the Support website.
Hot Swappable
The Genius Gateway requires an external 24Vdc power
supply and does not draw power from the Rx3i backplane.
Swapping out the GCG001 will therefore not impact the PLC.
However, this cannot be performed without disconnecting its
power supply. If configured to support Genius Hot Standby,
the loss of a single GCG001 will be tolerated; otherwise not.
For system standards, general operating specifications, and installation requirements, refer to
the
PACSystems RX3i System Manual
, GFK-2314.