Chapter 1. Introduction
6
PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual
GFK-2571N
1.3
PNC001 Module Specifications
PROFINET Support
PROFINET Version 2.2 General Class A IO-Controller
Redundantly controlled operation conforms to PROFINET V2.3 Type S-2
System Redundancy.
Note that the CPE100/CPE115 is a simplex PROFINET IO-Controller.
CPU Compatibility
Requires CPU315, CPU320, CPE305, CPE310 or CPE330 with firmware
version 7.0 or higher. Also compatible with all versions of CPE302.
Simplex or redundantly-controlled PROFINET I/O requires CRU320 release
8.00 or higher.
For the current status of CPE330 features refer to
PACSystems RX7i, RX3i
and RSTi-EP CPU Reference Manual
, (GFK-2222Z or later).
Note that CPE400 and CPE100/CPE115 features an embedded PROFINET
IO-Controller; these are standalone CPUs and do not support
IC695PNC001.
Power Requirements
1
,
Rev.
–
Ax
:
Rev.
–
Bxxx:
with no SFP devices installed
3.3Vdc: 0.5A
3.3Vdc: 0.5A
with two SFP devices installed, 0.35A per SFP
3.3Vdc: 1.2A maximum
3.3Vdc: 1.2A maximum
5 Vdc: 1.5A maximum
5 Vdc: 0.75A maximum
Operating Temperature Range
Rev. -Axxx
:
0°C to 60°C
Rev. -Bxxx
:
-25°C to 60°C
Note:
See section 1.4 for de-rating conditions
Number of PROFINET Port Connectors
PNC001
–
2 RJ45 and 2 SFP Cages located on the underside of module
(SFP devices not included, available separately).
Embedded PROFINET IO-Controller
–
2 RJ45.
Front Panel Connectors
PNC001-Ax: One micro USB for communication with a computer using
Command Line Interface.
PNC001-Bxxx: One RJ45. Disabled.
Command Line Interface Supported
PNC001-Ax
–
Yes. PNC001-Bxxx: No.
Embedded PROFINET IO-Controller
–
No.
LAN
IEEE 802.2 Logical Link Control Class I
IEEE 802.3 CSMA/CD Medium Access Control 10/100/1000 Mbps
Maximum I/O Memory
128 Kbytes of combined input/output memory per PROFINET Controller
Note:
RSTi-EP CPE100/CPE115 supports a maximum of 8 IO Devices.
The combined input and output memory is equivalent to the input
/output memory requirements of those 8 devices.
Hot-swappable
PNC001
–
Yes;
Embedded PROFINET IO-Controller
–
No.
CPU Status Bits
32
PROFINET IO-Device Data Update Rates
on the PROFINET Network
Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms and
512ms
Note:
For CPE100/CPE115, Update Rates below 16ms are not
recommended.
Number of IP Addresses
One
Number of MAC Addresses
PNC001
–
5. One per external PROFINET port and one internal.
Embedded PROFINET IO-Controller
–
1.
1
For CPE400, CPE330 and CPE100, CPE115 refer to the equivalent product specifications in the
PACSystems RX7i, RX3i and
RSTi-EP CPU Reference Manual
, (GFK-2222Z or later).