Chapter 5. Diagnostics
GFK-2571N
May 2018
103
5.1.2
Problems During Power-up and Reset
Certain conditions can prevent the module from powering up and becoming operational or entering firmware
update mode:
Problem
Indication
Action
Hardware failure
All LEDs off. Module unresponsive.
Return the module to
Automation & Controls
at GE Energy
Connections
.
Invalid bootstrap image
Invalid boot image
▪
No LEDs turn on and the module is
unresponsive, or
▪
The
STATUS
LED is solid green and is the
only LED that is on.
Power-up diagnostics/hardware
initializations fail that are
considered fatal
LED Fatal Error blink code, as described in this
chapter.
Note the blink code
and contact Customer
Service.
Non-Fatal diagnostic/hardware
initialization faults
The module continues normal power-up, but an
entry is added to the Local Log table and the
RX3i CPU’s
Fault Table (if backplane
communications have been established).
Note the fault and
contact Customer
Service.
The module does not contain
hardware identity information
LED Fatal Error blink pattern, as described in
this chapter.
Note the blink code
and contact Customer
Service.
5.1.3
Transitioning to Firmware Update Mode
The module transitions to firmware update mode for any of the following reasons:
1.
WinLoader has commanded the module to enter firmware update mode. This is normal when a firmware
update has been initiated from WinLoader.
2.
The PNC001 does not have a valid firmware image at power-up. The PNC001 performs checks to
determine the firmware image is valid and has not been corrupted before it begins execution. If the
validation fails, firmware update mode is activated until a valid image has been stored.
For more information about firmware update mode and using WinLoader, please see Chapter 2,