Chapter 3. Configuration
GFK-2571N
May 2018
55
3.4
Configuring PROFINET System Redundancy
To enable PROFINET System Redundancy in a CPE400 project, select the CPE400 target in the PME
Navigator and use the Property Inspector to change the
Enable Redundancy
target property to True.
To enable PROFINET System Redundancy in a CPE330 project, select the CPE330 target in the PME
Navigator and use the Property Inspector to change the
Enable Redundancy
target property to True.
The
Dual HWC
property then defaults to True and must remain True.
To enable PROFINET System Redundancy for a PNC001, select the CPE330 or CRU320 target in the
PME Navigator and use the Property Inspector to change the
Enable Redundancy
target property to
True. The
Dual HWC
property then defaults to True and must remain True.
Figure 35: Setting PROFINET System Redundancy Parameters in PME Inspector
CPE100/CPE115 does not support PROFINET System Redundancy.
Note:
For LED behavior and operator-initiated Role Switching in Hot Standby Systems, refer to the Quick
Start Guide or product manual of the device itself. These topics are not covered in this manual.