Chapter 9. Diagnostics
GFK-2950C
February 2018
391
9.3.1
System Fault References
When a system fault reference is set, additional fault references are also set. These other types of
faults are listed in
Fault References for Configurable Faults
Fault References for Configurable Faults
Fault
(Default
Action)
Address Description
May Also Be Set
#SBUS_ER
(diagnostic)
%SA0032 System bus error. All system bus error faults
are logged as informational.
#HRD_FLT, #SY_PRES,
#SY_FLT
#SFT_IOC
13
(diagnostic)
%SA0029 Non-recoverable software error in an I/O
Controller (IOC).
#IO_FLT, #IO_PRES,
#SFT_FLT
#LOS_RCK
14
(diagnostic)
%SA0012 Loss of rack (BRM failure, loss of power) or
missing a configured rack.
#SY_FLT, #SY_PRES,
#IO_FLT, #IO_PRES
#LOS_IOC
15
(diagnostic)
%SA0013 Loss of I/O Controller or missing a configured
Bus Controller.
#IO_FLT, #IO_PRES
#LOS_IOM
(diagnostic)
%SA0014 Loss of I/O module (does not respond), or
missing a configured I/O module.
#IO_FLT, #IO_PRES
#LOS_SIO
(diagnostic)
%SA0015 Loss of intelligent module (does not respond),
or missing a configured module.
#SY_FLT, #SY_PRES
#IOC_FLT
(diagnostic)
%SA0022 Non-fatal bus or I/O Controller error, more than
10 bus errors in 10 seconds. (Error rate is
configurable.)
#IO_FLT, #IO_PRES
#CFG_MM
(fatal)
%SA0009 Configuration mismatch. Wrong module type
detected. The CPU does not check the
configuration parameter settings for individual
modules such as Genius I/O blocks.
#SY_FLT, #SY_PRES
#OVR_TMP
(diagnostic)
%SA0008 CPU temperature has exceeded its normal
operating temperature.
#SY_FLT, #SY_PRES
Note:
If the fault action for a fault logged to the fault table is informational, the configured action is
not used. For example, if the logged fault action for an SBUS_ERR is informational, but you
configure it as fatal, the action is still informational.
13
The #SFT_IOC software fault will have the same action as what you set for #LOS_IOC.
14
When a Loss of Rack or Addition of Rack fault is logged, individual loss or add faults for each module in that rack are
usually not generated.
15
Even if the #LOS_IOC fault is configured as Fatal, the CPU will not go to STOP/FAULT unless both GBCs of an internal
redundant pair fail.