Chapter 9. Diagnostics
392
PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual
GFK-2950C
Fault References for Non-Configurable Faults
Fault
Address
Description
Result
#PS_FLT
%SA0005 Power supply fault
Sets #SY_FLT, #SY_PRES
#HRD_CPU
(fatal)
%SA0010 CPU hardware fault (such as failed
memory device or failed serial port).
Sets #SY_FLT, #SY_PRES, #HRD_FLT
#HRD_SIO
(diagnostic)
%SA0027 Non-fatal hardware fault on any module in
the system, such as failure of a serial port
on a LAN interface module.
Sets #SY_FLT, #SY_PRES, #HRD_FLT
#PNIO_
ALARM
%SA0030 A diagnostic PROFINET alarm has been
received and an I/O fault has been logged
in group 28.
Sets #ANY_FLT, #IO_FLT, #IO_PRES
#SFT_SIO
(diagnostic)
%SA0031 Non-recoverable software error in a LAN
interface module.
Sets #SY_FLT, #SY_PRES, #SFT_FLT
#PB_SUM
(fatal)
%SA0001 Program or block checksum failure during
power-up or in RUN Mode.
Sets #SY_FLT, #SY_PRES
#LOW_BAT
(diagnostic)
%SA0011 The low battery indication is not
supported for all CPU versions. For details,
refer to
Sets #SY_FLT, #SY_PRES
#OV_SWP
(diagnostic)
%SA0002 Constant sweep time exceeded.
Sets #SY_FLT, #SY_PRES
#SY_FULL
#IO_FULL
(diagnostic)
%SA0022 Controller fault table full (64 entries).
I/O Fault Table full (64 entries).
Sets #SY_FLT, #SY_PRES, #IO_FLT,
#IO_PRES
#APL_FLT
(diagnostic)
%SA0003 Application fault.
Sets #SY_FLT, #SY_PRES
#ADD_RCK
(diagnostic)
%SA0017 New rack added, extra rack, or previously
faulted rack has returned.
Sets #SY_FLT, #SY_PRES
#ADD_IOC
(diagnostic)
%SA0018 Extra IOC, previously faulted I/O Controller
is no longer faulted.
Sets #IO_FLT, #IO_PRES
#ADD_IOM
(diagnostic)
%SA0019 Extra IO module, or previously faulted I/O
module is no longer faulted.
Sets #IO_FLT, #IO_PRES
#ADD_SIO
(diagnostic)
%SA0020 New intelligent module is added, or
previously faulted module no longer
faulted.
Sets #SY_FLT, #SY_PRES
#IOM_FLT
(diagnostic)
%SA0023 Point or channel on an I/O module; a
partial failure of the module.
Sets #IO_FLT, I#O_PRES
#NO_PROG
(information)
%SB0009 No application program is present at
power-up. Should only occur the first time
the PACSystems controller is powered up
or if the user memory containing the
program fails.
CPU will not go to RUN Mode; it
continues executing STOP Mode
sweep until a valid program is loaded.
This can be a
null
program that does
nothing. Sets #SY_FLT and #SY_PRES.
#BAD_RAM
(fatal)
%SB0010 Corrupted program memory at power-up.
Program could not be read and/or did not
pass checksum tests.
Sets #SY_FLT and #SY_PRES.