background image

Use  the  following  procedure  to  install  the  UVR  accessory 
into  the  UVR  slot  in  the  accessory  compartment  of the 
circuit breaker:

Open

 

the

 

hinged

 

door

 

over

 

the

 

accessory  compart

-

ment and Trip Unit.
To  remove an  existing accessory module, loosen the 
accessory locking screw and pull the module out with 
the  Rating  Plug  Removal  Tool  (catalog  number 
TRTOOL).
Insert  the  UVR  accessory  into  the  proper  slot,  as 
illustrated in Figure 3. The UVR accessory is keyed for 
the correct slot in the accessory compartment. If the 
accessory cannot be fully seated in the compartment, 
check that the compartment position is correct.

Tighten the locking screw on the front of the accessory  
until it is snug (torque of 9 in-lb.)

CAUTION:

 Overtightening the locking screw may damage 

or distort the case of the accessory.

ATTENTION:

  Le  serrage  excessif  de  la  vis  de  verrouillage 

peut déformer le boîtier d’accessoire.

If the breaker is equipped with a MicroVersaTrip Plus 
or MicroVersaTrip PM Trip Unit, the UVR accessory can 
be  configured to  activate installed Bell  Alarm  Alarm 
Only  or  Bell  Alarm  with  Lockout accessories when  a 
UVR trip occurs, with the procedure described in  the 
Accessory Configuration section.
Connect the control wiring for the UVR to terminals 29 
and 30 at the terminal block on  the right side of the 
breaker.
Test the UVR to ensure proper operation, according to 
the procedures below.
Reconnect power to the circuit breaker and any other 
accessories.

Accessory Configuration

This section only applies if Bell Alarm–Alarm Only or Bell Alarm 
with  Lockout  accessories  are  installed  in  the  breaker,  along 
with a MicroVersaTrip Plus or MicroVersaTrip PM Trip
Unit. If  the  breaker is  equipped  with  a  Power+  Trip  Unit, the 
factory default settings, listed in Table 2, can not be changed.
The  UVR  accessory  can  be  configured  to  activate  the  Bell 
Alarm–Alarm Only  or  Bell  Alarm with Lockout accessories if  a 
UVR trip occurs. The configuration can be changed by removing 
the Trip Unit from the breaker, setting the DIP switches on the 
rear  of  the  Trip  Unit,  and  reinstalling the  Trip  Unit.  Figure  4 
illustrates the Trip Unit read DIP switches and their functions. 
Table 2 lists the switch functions and the factory settings for 
each.

Switch Factory

Setting

Function

1

Disabled Shunt trip activates Bell Alarm–Alarm

Only

2

Disabled UVR trip activates Bell Alarm–Alarm

Only

3

Enabled Protection trip activates Bell

Alarm–Alarm Only

4

Disabled Shunt trip activates Bell Alarm with

Lockout

5

Disabled UVR trip activates Bell Alarm with

Lockout

6

Enabled Protection trip activates Bell Alarm

with Lockout

2


Figure 3. Inserting the Undervoltage Release into the accessory compartment.

Figure 4. Accessory switch on the rear of the MicroVersaTrip Plus™ or MicroVersaTrip PM™ Trip Unit, 
showing the factory settings (solid part indicates that the switch is pushed in on that side).


Table 2. Accessory  switch settings, including the factory defaults.

4.

5

.

6

.

7

.

8

.

3.

2.

1.

Close  and  lock  or  seal  the  door  over  the  accessory 

compartment  and  Trip  Unit  to  prevent  unauthorized 

changes  to  Trip  Unit  settings  and  to  keep  contaminants 

out of empty accessory slots.

9

.

Summary of Contents for Power Break II SPUV012DC

Page 1: ...800 4000 ampere frame Power Break II circuit breakers This accessory trips the circuit breaker when the input control voltage drops to 35 60 of its rated value and prevents an open breaker from closing until the input control voltage is greater than 80 of the rated value In addition to providing a trip signal to the breaker the UVR accessory can be set up to interact with other Power Break II acce...

Page 2: ...nfiguration This section only applies if Bell Alarm Alarm Only or Bell Alarm with Lockout accessories are installed in the breaker along with a MicroVersaTrip Plus or MicroVersaTrip PM Trip Unit If the breaker is equipped with a Power Trip Unit the factory default settings listed in Table 2 can not be changed The UVR accessory can be configured to activate the Bell Alarm Alarm Only or Bell Alarm w...

Page 3: ...breaker cover Remove the cover from the breaker face Pull the Trip Unit locking lever to the right then hold the Trip Unit near the battery cover and lift it straight out of the breaker 3 4 6 7 8 Refer to Figure 4 and Table 2 to determine the switches to be changed Push in the appropriate Enable or Disable side of the switch Confirm all switch settings before reinstalling the Trip Unit in the brea...

Page 4: ...k that the polarity of the control power matches that shown on the label of the UVR accessory Note thatan otherwise unpowered Trip Unit would be powered up by an energized UVR accessory Verify that the breaker is closed Check that the UVR control power has been removed or that its voltage is less than 35 of the rated value Check that the UVR accessory is completely inserted Check that the Trip Uni...

Reviews: