Accessories
Padlock Device (Standard)
Padlocking devices a re standard on all Power Break® II Cir
cuit breakers. When the breaker is in the open position, and
the padlock device is raised at least %", the breaker cannot
be closed mechanically or electrically. The device accepts
up to three padlocks with 1/4" to 3/8" diameter shanks. The
padlock device meets the EUSERC requirement for
padlocking.
Integral padlock device
Key I nterlock Provisions
The key interlock provision enables the user to mount a
one-to four-cylinder, narrow-faced, Kirk-type FN customer
supplied lock on the face of the breaker. The key interlock
provision works in conj unction with the padlock device. The
key interlock extends a lever through the padlock device
when the key is turned to the key removal or bolt extended
position.
Key interlock insta lled on front of the breaker
30
Table
30.1
Key I nterlock Provisions
Catalog
Number of
Kirk Key lock
Superior Cat.
Number
Locks
Cat. Number
Number
SPK4
1
KFN00001-CD
S105827Y
SPK4
2
KFN00002-CD
S105828Y
SPK4
3
KFN00003-CD
S105829Y
SPK4
4
KFN00004-CD
S105827-4Y
CD Final digit may be 0, 1, 2, or 3 depending on number of key removal
positions.
Door Interlock
The door i nterlock provides interlocking of the circuit breaker
compartment's hinged door so that the breaker must be in
the "OFF" position before the door can be opened. The door
interlock is defeatable with a small tool to allow a uthorized
access. The catalog number of the door interlock is: SPOIL.
Door interlock
www . ElectricalPartManuals
. com
www
. ElectricalPartManuals
. com