Physica l Data
Power Break® II 800-Amp Drawout
56
2.88 [ 73.2)
DI S C ONNECTED
P O S I T I ON
�i;r [igs�1-loN
FACE OF
BREAKER
I " 25
OIA CLEARANCE HOLE R E Q U I R E D
MI�IMUM
I N ANY COMPART�(NT
O I Y I DER O R
S H E E T
METAL
1. All outline dimensions are the some for manually and electrically operated devices.
2. Dimensions in brackets are in [millimeters].
3. Any compartment metal in 6.50
X
14.00 [165.1
x
355.6] area below land above at 1600A, minimum stacking height) must be removed. Refer ence
U L891 dead-front switchboards standard-electrical spacing requirements.
4. 3.74 [ 95] minimum distance above substructure to any metal in an are 5.31
x
16.00 [134.9
x
406.4] due to arc chamber venting.
5. Customer's location for drilling hole for horizontally or vertically interconnected mechanical interlock. See bottom or side view