Physica l Data
Power Break® I I I nformation, 800-2000-Amp Frames
Table 1
Frome
Rating
800A
1600A
2000A
800A
1600A
2000A
DOOR
VENTS
CREF l
Breaker
Type
Stationary
Mounted
Drawout
Mounted
N/ A = Not Applicable
I
I
- - - - -
+
- - - - -
1
RECOYIIENOED DOOR
CUT- OUT
FOR 800. 1600
�ND
2000A FRAil[ SIZE
CIRCUIT BREAJ<ERS
Weight
Minimum
Minimum Door
Breaker
Comportment
Ventilation
Drowout
Volume
Substructure
71 1bs.•
None
[32,3
kg]
60.0 sq.
ln.
[387,1 sq. em] Total
3447 cu. in.
30.0 sq. in. [193,5 sq. em] Top
N/A
106lbs.
[56486 cu. em]
30.0 sq. 1n. [193,5 sq. em] Bottom
[48,2 kg]
86.4 sq. 1n. [557,4 sq. em] Total
43.2 sq. in. [278,7 sq. em] Top
43.2 sq
1n.
[278.7 sq. em] Bottom
106 1bs.
•
54 lbs
None
[48,2 kg]
[24 5 kg]
3780
CU. ln.
[61943 cu. em]
None
125 lbs:
68 1bs.
34.2
sq. in. [220,6 sq. em] Total
[56,8 kg}
[30,9 kg]
5670
cu.
1n.
[92915
cu. em]
29.5 sq. 1n. [190,3 sq. em] Tap
4.66 sq. in. [30,0 sq. em] Bottom
•
Add 9 lbs.
[4. 1 kg]
fo
r
electrical operator
1.
Dimensions in brackets ore [metric].
2. Bus bars or cables should be sized per
UL891
dead-front switchboards standard.
60
OF DRAWOUT
ONLY
Standard Door Cut-Out
A
B
10
14
[254]
[3 56}
Tnm Plate Requ1red
10
14
[254]
[356]
Tnm Plate Required
c
1.69
[42.9]
N/A
Optional Door Cut- Out
A
B
c
9.83
13.38
1.605
[249.7]
[339.9]
[40.8]
Flush Front or Non-hmged
Door Construction - Trim Plate may
be omitted
9.83
13.38
N/A
[249.7]
[339 9]
Flush Front or Non·hlnged
Door Construction · Tnm Plate may
be om1tted