CAUTION:
The breaker must be
OFF
before it i s
connected. If the breaker is charged, press the
ON
button to close the breaker contacts, then press the
OFF
button to open the contacts.
ATTENTION:
Le disjoncteur doit etre en position
OFF
avant qu'il ne soit embroche. Si le ressort de
fermeture du disjoncteur est charge, fermer les
contacts du disjoncteur par action sur le bouton
ON,
puis appuyer sur le bouton
OFF
pour ouvrir les
contacts.
4.
Engage the 1/.2-inch square end of the racking
shaft with the supplied wrench, catalog number
TDORT, and rotate the shaft clockwise to draw the
breaker into the
TEST
or
CONNECTED
position,
as illustrated in Figure
7.
The compartment
position indicator is shown in Figure 8.
NOTE:
If the breaker does not fit the structure, check
the rejection relationship, illustrated in Figure 8,
to
verify that a correctly rated breaker is being
installed. Table
1
lists the correct draw-out substruc
ture for each breaker frame.
NOTE:
Si le disjoncteur ne rentre pas dans le berceau,
verifier le detrompeur illustre dans les figure 8, qui
empeche !'insertion
d'un mauvais
calibre
de
disjoncteur.
La
Table
1
definis le berceau convenable
a
chaque taille de disjoncteur.
Figure
4.
Lifting Bar attached to a draw-out breaker for manual lifting.
3
Power Break® II Circuit Breakers
Draw-Out Breaker Installation
Figure
5
Lifting Bar attached to a draw-out breaker for lifting with a
hoist.
Figure
6
Breaker installed on rails, ready to be pushed into the
substructure.
www
. ElectricalPartManuals
. com