Figure 1. Old terminal board mounted on the breaker (2500–4000 A 

shown).  

7. 

Push in the locking lever on the side of the trip unit 

mounting plate and carefully lift off the trip unit. 

8. 

Remove the trip unit mounting plate as follows for 

the appropriate breaker frame size: 
• 800–2000 A: Remove the two mounting screws on 

the trip unit plate and loosen the 

1

/

4

-20 screw on 

the side of the assembly, as shown in Figure 2. 

Remove the trip unit mounting plate assembly. 

• 2500–4000 A: Remove the two screws securing the 

trip unit mounting plate to the center-phase sensor 

shell, as shown in Figure 3. Lift off the trip unit 

mounting plate. Take care that the two nuts in the 

slots in the top of the CT don’t fall out. 

9. 

Use pliers to bend the two locking tabs that secure 

the large plug to the trip unit mounting plate, as 

shown in Figure 4. Slide the plug off the mounting 

plate, then remove and save the plug mounting 

bracket. 

10. 

Connect the leads from the new terminal board [1] 

to the large plug, as shown in Figure 5, according to 

the wiring diagram in Figure 6. Use AMP tool 

455822-2 to remove incorrectly placed pins from the 

plug. 

 

Figure 2. Trip unit mounting plate on an 800–2000 A breaker. 

 

Figure 3. Trip unit mounting plate on a 2500–4000 A breaker. 

 

Figure 4. Bending the locking tabs to remove the large plug from the 

trip unit mounting plate. 

 

Figure 5. Connecting the leads from the new terminal board to the trip 

unit plug. 

1/4-20 

Mounting 

Screw 

Mounting

Screws 

Mounting 

Screws 

Summary of Contents for Power Break

Page 1: ...8 TDOSVD907F Trip unit disconnect breaker 1 9 TDOSVD12 Trip unit disconnect substructure 1 10 Incl with 9 Spring 1 Table 3 List of parts in the power management upgrade kit for 800 2000 A draw out br...

Page 2: ...re that the two nuts in the slots in the top of the CT don t fall out 9 Use pliers to bend the two locking tabs that secure the large plug to the trip unit mounting plate as shown in Figure 4 Slide th...

Page 3: ...is present in a 2500 4000 A breaker remove and save the inner bolt lock washer and flat washer on the C phase contact assembly as shown in Figure 9 3 Figure 6 Wiring diagram for terminal board and tri...

Page 4: ...own in Figure 12 4 14 File three slots in the breaker base as shown in Figure 13 to accommodate the auxiliary switch wires 15 Run the five remaining auxiliary switch cables out through the slots in th...

Page 5: ...ure 18 Use small wire ties 5 as shown to dress the wire bundles 19 Slide the mounting bracket onto the large trip unit plug and slide the bracket over the two pins on the trip unit mounting plate as s...

Page 6: ...forming screws 7 supplied as shown in Figure 23 Run the wires through the hole in the plate to the terminal board 24 Connect the wires from the breaker mounted trip unit disconnect 8 to the terminal...

Page 7: ...05 106 red white blue power management 3 7 10 107 108 109 black red power management 4 8 110 111 Table 5 Wire groupings from the trip unit disconnect Spring Mounting Hole Figure 25 Placing the trip un...

Page 8: ...o its cubicle or substructure g These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installatio...

Reviews: