As shown in 

Figure 1

 below, dataline switches are numbered

sequentially beginning with 01-01 (Panel 01-Switch 01). A
single switch unit may have 1, 2, 4 or 8 buttons. Switch units
should be identified on the reflected ceiling plan showing the
number of buttons in each location. Check to confirm that the
correct switch unit has been installed at each location.

A separate 

ProSys SWITCH DOCUMENTATION

 form

should be used for each relay panel to record the number of
the switch and its number of buttons. Allow one line for each
button as shown on the form in 

Figure 2

 below. For example,

switch 01-01 has four buttons. The form should list all buttons
on each switch, even if you are not using all of them.

NUMBER AND DOCUMENT DATALINE SWITCHES

Any switch button may be softwired to control a single relay
or a group of relays within any single panel (see next page for
softwiring a dataline switch). For example, assume that you
want the top two buttons of a 4-button switch to control open
office areas associated with relays in Panel 01, while the

third button controls common areas (rest rooms and hallways)
in Panel 02. The form below shows how to record this intent
and also shows the labeling for each switch button. Finally,
write the switch number on the label in the lower right corner
of the switch base (see 

Figure 4

 on page 5).

Figure 1

DATALINE SWITCH DOCUMENTATION

SWITCH # BUTTON

RELAYS CONTROLLED

DESCRIPTION

 (8 

MAX

.)

-01

1

-01, -02

OFFICE - NW

"

2

-03, -04

OFFICE - NE

"

3

SPARE

"

4

    "

-02

1

-15, -16

HALLWAYS NORTH

"

2

-17, -18

HALLWAYS SOUTH

Figure 2

PANEL #

01

01-01

01-02

02-01

02-02

01-03

01-04

02

xx

PANELS 
NUMBERED 
SEQUENTIALLY 
BEGINNING 
AT 01

DATALINE
18/4 AWG
1500 FT. MAX.
GE RLONWIRE-4P

DATALINE SWITCHES FOR EACH PANEL
NUMBERED SEQUENTIALLY (PANEL #-SWITCH #)

MAXIMUM TOTAL NUMBER OF RELAY PANELS AND DATALINE SWITCHES IS 64

SWITCH
BUTTONS
(#1 AT TOP)

RELAY

PANEL

RELAY

PANEL

RELAY

PANEL

01

Summary of Contents for ProSys DEH40206

Page 1: ... period Dip switch 4 must be in the off position to enable this feature as shown on page 8 Order this feature by adding a K to the part number for the 1 2 4 and 8 button switch For example RS2PSxK Any button on a Softwire Switch may be softwired to Any relay or group of relays within a single relay panel A channel within a single relay panel The same channel among multiple panels requires an RCLK8...

Page 2: ...nch twist lay on pairs 6 inch twist lay on cable Plenum rated copolymer jacket 0 230 O D FEP 0 010 insulation 0 060 O D 30 pF foot maximum capacitance 20 C to 150 C operating temperature range 17 lbs per 500 foot reel UL rated If you have purchased the ProSys Lighting Control System the stand alone system the devices panels switches and clock will be in self install mode This means that as soon as...

Page 3: ...tween the red and black terminals on the last switch It should be less than 3 ohms If it is higher work backwards toward the relay panel checking the resistance at each switch to find the bad connection When finished reconnect the Local Dataline at the panel Shorted Dataline After the dataline resistance test checks out you can easily test for a shorted dataline by measuring the resistance from re...

Page 4: ... single panel see next page for softwiring a dataline switch For example assume that you want the top two buttons of a 4 button switch to control open office areas associated with relays in Panel 01 while the third button controls common areas rest rooms and hallways in Panel 02 The form below shows how to record this intent and also shows the labeling for each switch button Finally write the swit...

Page 5: ...t it provides a simple way of manually overriding all of the relays which are grouped to an automation channel A H within a panel With the wallplate removed and the switch s master button flipped open 1 Press the SOFTWIRE tab The LED next to the tab will turn on then the individual button LEDs will start flashing 2 Press the switch button you want to softwire Master Button on an RS1PS x The LED fo...

Page 6: ...t Lift the button out twisting it slightly if necessary to free the small hook holding the center edge of the button in place To replace the button position the small center hook in place and press the hinge pin into the hinge bracket until it snaps in place Remove Replace Screwless Wallplate To remove the screwless cover plate press in the black tab at the bottom edge of the plate and lift the pl...

Page 7: ...Figure 7 shows how the four buttons on a quad switch would be softwired to create this switching function All of the buttons are wired as Patterns Reviewing the LED operation shows why this is important see Figure 6 When the occupant toggles the top button ON relay 01 01 will turn ON and relay 01 02 will turn OFF to give 1 3 lighting The LED for 1 3 will turn on red Pressing the second button caus...

Page 8: ...here Pressing the Master Button again would restore the lighting in the two zones which had been on without having to turn on the entire floor You can change the operating scenario of the Master Button using the first two DIP switches located on the back of the switch The DIP switches are normally covered by a label to prevent accidental changes As shown above the factory default setting is all DI...

Page 9: ... button 1 controlling a Pattern in which the north half of the floor is ON and south half is OFF The second button does just the reverse With this combination whenever the cleaners turn on one half of the floor the other half turns off automatically saving half the lighting Furthermore since switch 01 01 has been configured as a cleaning switch the cleaning crew cannot accidentally put an occupant...

Page 10: ......

Reviews: