GFK-2306E
Chapter 3 Installation Procedures for Conformance and Compliance
3-5
3
Mounting the QuickPanel View in a Panel
1. Insert the unit into the panel cutout (without a CF card in the CF port).
2. Insert the hook of each mounting clamp into the housing openings as
shown below.
3. Ensure that the gasket is properly seated in the bezel channel and firmly
tighten the clamp screws.
Note:
The torque range for the mounting clamp screws is 2.6
–4.4 inch/lbs
(0.3
–0.5 Nm).
The mounting clamps hold the unit in place by tension. No drilling is required.
Do not damage the gasket attached to the back of the QuickPanel. This gasket
prevents shock hazards and damage caused by liquids accidentally entering
the unit after installation.
Also, limit the number of times you remove and reinstall the unit. Too many
installations may cause
gasket “set” and degradation of the seal.
Summary of Contents for QuickPanel+ IC754VSI12CTD
Page 4: ......