GFK-2306E
Appendix A Specifications
A-5
A
Environmental
Operating Temperature*
32°F to 122°F
(0°C to 50°C)
Operating Humidity
10% to 85% non-condensing
Storage Temperature*
-4 to 158°F
-20 to 70°C
Storage Humidity
10% to 85% non-condensing RH (non-condensing)
at less than 50°C; maximum 50% RH at greater
than 50°C.
NEMA Rating
4 and 4x when mounted in a comparably rated
NEMA panel (NEMA 4 is approximately equivalent
to IP66; visit www.nema.org)
Operational Vibration
IEC 60068-2-6
10
—57Hz, 0.012" peak to peak displacement
57
—500Hz, 1.0g acceleration
Operational Shock
IEC 60068-2-27
15g, 11ms (sine wave)
*
Rated temperature limits refer to the ambient air temperature immediately
surrounding (less than 3‖ or 7.6 cm) the QuickPanel inside the enclosure in which
the QuickPanel is mounted. Additional provisions for remaining within the stated
limits must be considered where additional, external thermal loads are imposed
on the QuickPanel. These could include large heat producing motor drives, or
power supplies in the same cabinet or in outdoor applications involving direct sun
exposure.
Battery
Type
Panasonic BR2032 (3V, 190mAh, lithium)
Approximate
5 years
Calendar/Clock
Resolution
1 second
Accuracy
±2 to 3 minutes per month
Retention
Life of battery