12
31-5000842 Rev. 0
INSTALLER MENU (cont)
INSTALLATION INSTRUCTIONS
Menu Item
(Mode advances
to next, Fan
returns to
previous)
Description
Default
Setting
Range/
Selections
(+ or - to
change)
8 Wire
Setting
Availability
2- Way
Setting
Availability
16
Deadband (F)
This offset is added to both
Cooling & Heating Differential 1
when in autochangeover mode
Note:
Setting is only available if
autochangeover is enabled
1
1 to 10
X
17
Min Cooling Temp (F)
Note:
Can't be a higher
temperature than setting 18
66
60, 64, 66,
68, 70, 72,
74, 76
X
18
Max Heating Temp (F)
Note:
Can't be a lower
temperature than setting 17
78
65, 70, 72,
74, 76, 78,
80, 85
X
19
Room Temp Offset (F)
If needed, this is an offset to
calibrate room temperature
reading
0
-9 to 9
X
X
20
Humidity Offset
If needed, this is an offset to
calibrate room humidity reading
0
-9 to 9
X
X
21
Occupancy Energy savings
OF =
No temperature setbacks
are allowed
Y =
Temperature setbacks are
allowed when no occupancy is
detected
S =
Scheduled Energy Savings.
Temperature setbacks are only
allowed in the time window
specified by settings 29 and 30.
Y
OF, Y, S
X
X
22
Occupancy Response Time
(tenths of a second)
1
0-30
X
X
24
Occupancy Cool Setback
Temperature
The number of degrees (F) the
temperature is allowed to drift
above setpoint in cooling with
no occupants detected
Note:
Only Available if
Occupancy Energy Savings
(setting 21) is set to Y or S
3
0-15
X
X
25
Occupancy Heat Setback
Temperature
The number of degrees (F) the
temperature is allowed to drift
below setpoint in heating with
no occupants detected
Note:
Only Available if
Occupancy Energy Savings
(setting 21) is set to Y or S
3
0-15
X
X
26
Not Used - For Future Use
5
0-15
X
27
Not Used- For Future Use
5
0-15
X