POWER CONNECTION CHART

GE 230/208 Volt

Wall Plug

Heater Wattage

Power Supply Kit

Configuration

Circuit Protective Device

@ 230/208 Volts

RAK3152

Tandem

15-Amp Time-Delay Fuse or Breaker

2.55/2.09 KW

RAK3202

Perpendicular

20-Amp Time-Delay Fuse or Breaker

3.45/2.82 KW

RAK3302

Large Tandem

30-Amp Time-Delay Fuse or Breaker

5.00/4.10 KW

230/208 VOLT ELECTRICAL SUPPLY

A power supply kit must be used to supply power to the
Zoneline unit. The appropriate kit is determined by the
voltage, the means of electrical connection, and the
amperage of the branch circuit. See the POWER
CONNECTION CHART to confirm the appropriate kit.

All wiring, including installation of the receptacle, 
must be in accordance with the NEC and local codes,
ordinances, and regulations.

Installation instructions

RAK3152, RAK3202,

for your new

RAK3302

Power Supply Kit for Cord
or Direct Connection

Before you begin – Read these instructions completely and carefully.
IMPORTANT – OBSERVE ALL GOVERNING CODES AND ORDINANCES.
Note to Installer – Be sure to leave these instructions with the Consumer.
Note to Consumer – Keep these instructions with your Owner’s Manual for future reference.

TOOLS NEEDED

1/4

Nut driver

Phillips screwdriver

Wire cutter (For direct connect applications only.)

This kit is for use with 230/208 volt 5200, 5500, and
7500 Series GE Zoneline units only.

IMPORTANT NOTES

This unit must be properly grounded.

The electrical rating marked on the previously installed
Zoneline and power supply kit must be the same as
the supply branch circuit.

Aluminum building wiring may present special
problems—consult a qualified electrician.

All wiring, including installation of the receptacle, 
must be in accordance with the NEC and local codes,
ordinances, and regulations.

Use ONLY the wiring size recommended for single
outlet branch circuit.

Proper current protection is the responsibility of 
the owner.

Tandem

15 Amp

230/208 volt receptacle configuration

Perpendicular

20 Amp

Large Tandem

30 Amp

Power supply kit

Recommended branch circuit wire sizes*

Nameplate

maximum circuit 

AWG wire

breaker size

size**

15A

14

20A

12

30A

10

AWG – American Wire Gauge

*

Single circuit breaker from main box

** Based on copper wire, single-insulated conductor at 60°C

NOTE:

Use copper conductors only.

CAUTION:

Disconnect the electrical power

supply before wiring connections.

Summary of Contents for RAK3152

Page 1: ...r Note to Consumer Keep these instructions with your Owner s Manual for future reference TOOLS NEEDED 1 4 Nut driver Phillips screwdriver Wire cutter For direct connect applications only This kit is for use with 230 208 volt 5200 5500 and 7500 Series GE Zoneline units only IMPORTANT NOTES This unit must be properly grounded The electrical rating marked on the previously installed Zoneline and powe...

Page 2: ...e Zoneline operation 2 FOR 230 208 VOLT POWER CORD CONNECTIONS ONLY FOR 7500 SERIES MODELS ONLY 1 Remove the front panel by removing the filter taking out the four front screws the upper two screws from the top of the panel and the shipping screws on each side if present Discard the two side shipping screws if present 2 Remove the junction box cover and the junction box and discard 3 Connect the p...

Page 3: ...are engaged 10 Dress the wiring inside the junction box and attach the cover plate with screws A and C 11 Reinstall the room cabinet front FOR 230 208 VOLT DIRECT CONNECT APPLICATIONS ONLY 3 3 4 3 Connector 6 Conduit 9 pin connector Unit 9 pin receptacle C A C A B C A C A FOR 7500 SERIES MODELS ONLY 1 Measure 7 down the cord from where it emerges from the back of the yellow 9 pin connector and cut...

Page 4: ... with some color other than green or white Connect the green lead of the power supply kit to the power supply and branch circuit ground 3 Phase 208 VAC with Crazy Leg When connecting the Zoneline to a three phase circuit with Crazy Leg for 208V applications Connect the white and black leads of the Zoneline power supply kit to the branch circuit Neutral and L1 leads The white lead of the power supp...

Reviews: